Replacing a Main Storage Disk Module (OceanStor Pacific 9950)

Half-palm NVMe SSDs are used as main storage disk modules to provide data storage space and are hot-swappable.

Impact on the System

Prerequisites

Precautions

When replacing a main storage disk module, ensure that the time from removing the main storage disk module to installing a new main storage disk module into the node does not exceed three minutes. Otherwise, the heat dissipation of the storage device will be affected and the system will be faulty.

Tools and Materials

Procedure

  1. Remove the front panel cover.

    Press the release button on the right of the front panel cover, tilt the front panel cover by 20° to 30° forward, and move the front panel cover rightward to separate it from the groove on the left of the system subrack. Then, remove the front panel cover. See (1), (2), and (3) in Figure 1.
    Figure 1 Removing a front panel cover

  2. Remove the faulty disk module.

    • When removing disk modules, correctly record the slots where disk modules reside.
    • The time from disk module removal to installation and restoration cannot exceed three minutes. Otherwise, the system will be faulty due to overtemperature.
    1. Press the ejector release button on the disk module. The ejector lever automatically ejects. See (1) in Figure 2.
      Figure 2 Removing a disk module
    2. Hold the ejector lever of the disk module and pull out the disk module slowly. See (2) and (3) in Figure 2.

  3. Put the removed disk module into an ESD bag.
  4. Take the replacement disk module out of its ESD bag.
  5. Install the replacement disk module.

    Ensure that disk modules are inserted into the same slots before and after the replacement. Otherwise, services may be affected.

    1. Open the ejector lever completely and push the disk module into the node along the slot until it cannot move forward. See (1) in Figure 3.
      Figure 3 Installing a disk module
    2. Close the ejector lever of the disk module to push the disk module into the node with the force between the ejector lever and the node. See (2) in Figure 3.

  6. Check the installation.

    After inserting the disk module, wait one minute and then check the disk module running indicator to determine whether the disk module has been successfully installed.

    If the disk module running indicator is steady green, the disk module is successfully installed. In this case, go to 7. Otherwise, the disk module fails to be installed and you need to perform the following operations to restore the installation:
    1. Check whether the disk module has been firmly inserted. If not, wait one minute and reinsert it.
    2. If the disk module still fails to be installed after you reinsert it, the link of the disk slot may be faulty. In this case, contact Huawei technical support.

  7. Install the front panel cover.

    Align the latch on the left of the front panel cover with the groove on the left of the system subrack, and push the right of the front panel cover forward until you hear a click. Ensure that the front panel cover is secured to the system subrack. See (1) and (2) in Figure 4.
    Figure 4 Installing a front panel cover

Follow-up Procedure

After the main storage disk module is replaced, label it to facilitate subsequent operations.