hardware=Hardware Status
software=Software Status
increment=Value-Added Services
unrecoveredalarm=Alarm Check

1.name = Controller enclosure status
1.0.name = Controller enclosure status
1.0.suggestion = 1. A controller enclosure is normal if the controller's Health Status is Normal and Running Status is Online. \n2 Otherwise, the controller enclosure is abnormal. In that case, contact Huawei storage R&D engineers for technical support.
1.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show controller general command. \nStep 3 Check the controller's status.
1.0.criterion = If the controller's Health Status is Normal and Running Status is Online, the controller enclosure is normal. Otherwise, it is abnormal.

2.name = Expansion enclosure status
2.0.name = Expansion enclosure status
2.0.suggestion = An expansion enclosure is normal if its Health Status is Normal and Running Status is Online. \n2 Otherwise, the expansion enclosure is abnormal. In that case, contact Huawei storage R&D engineers for technical support.
2.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show enclosure command to check the expansion enclosure's status.
2.0.criterion = If the expansion enclosure's Health Status is Normal and Running Status is Online, the expansion enclosure is normal. Otherwise, it is abnormal.

3.name = Power module status
3.0.name = Power module status
3.0.suggestion = 1. If a power module's Health Status is Fault, replace the power module. \n.2. If the power module's Health Status is No Input, check whether the power cable is properly inserted. If the power cable is properly inserted, check whether the power cable properly carries power. If power is properly supplied, replace the power module. \n3. If you have any questions, contact Huawei storage R&D engineers for technical support.
3.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show power_supply command to check the power module's status.
3.0.criterion = If the power module's Health Status is Normal and Running Status is Online, the power module is normal. Otherwise, it is abnormal.

4.name = BBU status
4.0.name = BBU status
4.0.suggestion = 1. If a BBU's Health Status is Fault, replace the BBU. \n2. If you have any questions, contact Huawei storage R&D engineers for technical support.
4.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show bbu general command to check the BBU's status.
4.0.criterion = If the BBU's Health Status is Normal and Running Status is Online, the BBU is normal. Otherwise, it is abnormal.

5.name = BBU lifecycle
5.0.name = BBU lifecycle
5.0.suggestion = 1. If the remaining life of a BBU is shorter than 60 days, replace the BBU as soon as possible. \n2 If you have any questions, contact Huawei storage R&D engineers for technical support.
5.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the developer command to go to the developer mode. \nStep 3 Run the show bbu life command to check the BBU's remaining life.
5.0.criterion = If the BBU's Remain Life Days is smaller than 60 days, the BBU is expiring and must be replaced as soon as possible.

6.name = Fan status
6.0.name = Fan status
6.0.suggestion = 1. If a fan's Health Status is Fault, replace the fan. \n2. If you have any questions, contact Huawei storage R&D engineers for technical support.
6.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show fan command to check the fan's status.
6.0.criterion = If the fan's Health Status is Normal and Running Status is Running, the fan is normal. Otherwise, it is abnormal.

7.name = Disk status
7.0.name = Disk status
7.0.suggestion = 1. If a disk is physically abnormal, replace the disk. \n2. If you have any questions, contact Huawei storage R&D engineers for technical support.
7.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show disk general command or show disk general|filterRow Health\sStatus not equal_to Normal or Running\sStatus not equal_to Online command to check the disk's status.
7.0.criterion = If the disk's Health Status is Normal, the disk is normal. Otherwise, it is abnormal.

8.name = Disk write cache status
8.0.name = Disk write cache status
8.0.suggestion = 1. The disk write cache is normal when its Write Cache Switch is Yes or No. \n2. If you have any questions, contact Huawei storage R&D engineers for technical support.
8.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the developer command to go to the developer mode. \nStep 3 Run the show disk write_cache command to check the disk write cache's status.
8.0.criterion = If Write Cache Switch is Yes or No, the disk write cache is normal. Otherwise, it is abnormal.

9.name = Disk NCQ status
9.0.name = Disk NCQ status
9.0.suggestion = 1. The disk NCQ is normal when its NCQ is Yes or No. \n2. If you have any questions, contact Huawei storage R&D engineers for technical support.
9.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the developer command to go to the developer mode. \nStep 3 Run the show disk ncq command to check the disk NCQ's status.
9.0.criterion = If NCQ is Yes or No, the disk NCQ is normal. Otherwise, it is abnormal.

10.name = Optical transceiver status
10.0.name = Optical transceiver status
10.0.suggestion = 1 An optical transceiver is normal when its Health Status is Normal. \n2. If you have any questions, contact Huawei storage R&D engineers for technical support.
10.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show port fibre_module command to check the optical transceiver's status.
10.0.criterion = If the optical transceiver's Health Status is Normal, the optical transceiver is normal. Otherwise, it is abnormal.

11.name = Controller enclosure temperature
11.0.name = Controller enclosure temperature
11.0.suggestion = 1 A controller enclosure is normal when its CPU Temperature(Celsius) is no more than 85\u2103 and entrance Temperature(Celsius) is no more than 52\u2103. \n2. If you have any questions, contact Huawei storage R&D engineers for technical support.
11.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the developer command to go to the developer mode. \nStep 3 Run the show controll general command to check the controller enclosure's temperature.
11.0.criterion = All Temperature(Celsius) vaules: If the controller enclosure's CPU temperature(the first value) is no more than 85\u2103 and entrance temperature(the second value) is no more than 52\u2103, the controller enclosure is normal. Otherwise, it is abnormal.

12.name = Expansion enclosure temperature
12.0.name = Expansion enclosure temperature
12.0.suggestion = 1 An expansion enclosure is normal when its Temperature(Celsius) is no more than 52\u2103. \n2. If you have any questions, contact Huawei storage R&D engineers for technical support.
12.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show enclosure command to check the expansion enclosure's temperature.
12.0.criterion = If the expansion enclosure's Temperature(Celsius) is no more than 52\u2103, the expansion enclosure is normal. Otherwise, it is abnormal.

13.name = FC port
13.0.name = FC port
13.0.suggestion = 1. It is normal that the FC ports on controllers A and B are both in the Normal state. \n2. If you have any questions, contact Huawei storage R&D engineers for technical support.
13.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show port general command to check the FC port's status.
13.0.criterion = 1. It is normal that the FC ports on controllers A and B are both in the Normal state. Otherwise, it is an abnormal situation. \n2. It is normal that the FC ports are not connected or their rate is 1000 Mbit/s, 2000 Mbit/s, 4000 Mbit/s, or 8000 Mbit/s. Otherwise, it is an abnormal situation.

14.name = SAS port
14.0.name = SAS port
14.0.suggestion = 1. It is normal that the SAS ports on controllers A and B are both in the Normal state. \n2. If you have any questions, contact Huawei storage R&D engineers for technical support.
14.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show port general command to check the SAS port's status.
14.0.criterion = 1. It is normal that the SAS ports on controllers A and B are both in the Normal state. Otherwise, it is an abnormal situation.

15.name = iSCSI port
15.0.name = iSCSI port
15.0.suggestion = 1. It is normal that the iSCSI ports on controllers A and B are both in the Normal state. Otherwise, it is an abnormal situation. \n2. It is normal that the iSCSI ports are not connected or their rate is 1000 Mbit/s or 10000 Mbit/s. Otherwise, it is an abnormal situation. \n3. If you have any questions, contact Huawei storage R&D engineers for technical support.
15.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show port general command to check the iSCSI port's status.
15.0.criterion = 1. It is normal that the iSCSI ports on controllers A and B are both in the Normal state. Otherwise, it is an abnormal situation. \n2. It is normal that the iSCSI ports are not connected or their rate is 1000 Mbit/s or 10000 Mbit/s. Otherwise, it is an abnormal situation.

16.name = Management network port connection status
16.0.name = Management network port connection status
16.0.suggestion = 1. It is normal that Management Port in ETH port is not connected or the port rate is 1000 Mbit/s. \n2. If you have any questions, contact Huawei storage R&D engineers for technical support.
16.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show port general command to check the management network port's connection status.
16.0.criterion = It is normal that Management Port in ETH port is not connected or the port rate is 1000 Mbit/s. Otherwise, it is an abnormal situation.

17.name = Partial disk fault isolation
17.0.name = Partial disk fault isolation
17.0.suggestion = 1. It is normal that there is no record for partial disk fault isolation. \n2. If you have any questions, contact Huawei storage R&D engineers for technical support.
17.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show disk bad_sector_record command to check for records for partial disk fault isolation.
17.0.criterion = It is normal that there is no record for partial disk fault isolation. Otherwise, it is an abnormal situation.

18.name = Front-end bit error
18.0.name = Front-end bit error
18.0.suggestion = 1. It is normal that both the ETH port and FC port do not have bit errors. \n2. If you have any questions, contact Huawei storage R&D engineers for technical support.
18.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the developer command to go to the developer mode. \nStep 3 Run the show port bit_error command to check for bit errors.
18.0.criterion = It is normal that both the ETH port and FC port do not have bit errors. Otherwise, it is an abnormal situation.

19.name = Expansion port bit error
19.0.name = Expansion port bit error
19.0.suggestion = 1. It is normal that no SAS port has bit errors. \n2. If you have any questions, contact Huawei storage R&D engineers for technical support.
19.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the developer command to go to the developer mode. \nStep 3 Run the show port bit_error command to check for bit errors.
19.0.criterion = It is normal that no SAS port has bit errors. Otherwise, it is an abnormal situation.

41.name = Product version
41.0.name = Product version
41.0.suggestion = 1. It is normal that the product version can be obtained. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
41.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show system general or show version all command to check the product version.
41.0.criterion = It is normal that Product Version is V100R001. Otherwise, it is an abnormal situation.

42.name = System software version
42.0.name =System software version
42.0.suggestion = 1. It is normal that the system  software version can be obtained and controllers A and B have the same version. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
42.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show version all or show controller general command to check the  System software  version.
42.0.criterion = It is normal that the  System software  version can be obtained and controllers A and B have the same version. Otherwise, it is an abnormal situation.

oftwareVersionHotpatch.name = Hot Patch Version Consistency
SoftwareVersionHotpatch.0.name = Hot Patch Version Consistency
SoftwareVersionHotpatch.0.suggestion = 1 Log in to the storage system as user admin.\n2 Run the change user_mode current_mode user_mode=developer command to enter the developer mode.\n3 Run the "delete hotpatch" command to delete the hot patch, then reinstall it. \n4 If you have any questions, please contact technical support engineers for further handling.
SoftwareVersionHotpatch.0.method = Step 1 Log in to the device as user admin.\nStep 2 Run the "show upgrade package" command to query the hot patch version (Current Version in HotPatch Version).
SoftwareVersionHotpatch.0.criterion = If the hot patch has not been installed on any controller or the hot patch versions of all controllers are the same, the check is passed, otherwise, the check is not passed.

43.name = BMC version
43.0.name = BMC version
43.0.suggestion = 1. It is normal that the BMC version can be obtained and controllers A and B have the same version. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
43.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show version all or show controller general command to check the BMC version.
43.0.criterion = It is normal that the BMC version can be obtained and controllers A and B have the same version. Otherwise, it is an abnormal situation.

44.name = SES version
44.0.name = SES version
44.0.suggestion = 1. It is normal that the SES version can be obtained and controllers A and B have the same version. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
44.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show version all or show controller general command to check the SES version.
44.0.criterion = It is normal that the SES version can be obtained and controllers A and B have the same version. Otherwise, it is an abnormal situation.

45.name = BIOS version
45.0.name = BIOS version
45.0.suggestion = 1. It is normal that the BIOS version can be obtained and controllers A and B have the same version. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
45.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show version all or show controller general command to check the BIOS version.
45.0.criterion = It is normal that the BIOS version can be obtained and controllers A and B have the same version. Otherwise, it is an abnormal situation.

46.name = PCB version
46.0.name = PCB version
46.0.suggestion = 1. It is normal that the PCB version can be obtained and controllers A and B have the same version. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
46.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show version all or show controller general command to check the PCB version.
46.0.criterion = It is normal that the PCB version can be obtained and controllers A and B have the same version. Otherwise, it is an abnormal situation.

47.name = Logic version
47.0.name = Logic version
47.0.suggestion = 1. It is normal that the Logic version can be obtained and controllers A and B have the same version. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
47.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show version all or show controller general command to check the Logic version.
47.0.criterion = It is normal that the Logic version can be obtained and controllers A and B have the same version. Otherwise, it is an abnormal situation.

48.name = BBU version
48.0.name = BBU version
48.0.suggestion = 1. It is normal that all BBUs have the same version. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
48.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show version all or show controller general command to check the BBU version.
48.0.criterion = It is normal that all BBUs have the same version. Otherwise, it is an abnormal situation.

51.name = Device SN
51.0.name = Device SN
51.0.suggestion = 1. It is normal that the device SN can be obtained and it meets the related requirements. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
51.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show system general command to check the device SN.
51.0.criterion = It is normal that the device SN can be obtained and it meets the related requirements. Otherwise, it is an abnormal situation.

61.name = LUN status
61.0.name = LUN status
61.0.suggestion = 1. A LUN is normal when its Health Status is Normal. \n2. If a LUN is abnormal, contact Huawei storage R&D engineers to repair the LUN.
61.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show lun command or show lun |filterRow Health\sStatus not equal_to Normal or Running\sStatus not equal_to Online command to check the LUN's status.
61.0.criterion = If the LUN's Health Status is Normal, the LUN is normal. Otherwise, it is abnormal.

62.name = Pool status
62.0.name = Pool status
62.0.suggestion = 1. A pool is normal when its Health Status is Normal and Running Status is Online. \n2. If a pool is abnormal, contact Huawei storage R&D engineers to repair the pool.
62.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show storage_pool general command to check the pool's status.
62.0.criterion = If the pool's Health Status is Normal and Running Status is Online, the pool is normal. Otherwise, it is abnormal.

63.name = Tier status
63.0.name = Tier status
63.0.suggestion = 1. A pool is normal when its Health Status is Normal. \n2. If a tier is abnormal, contact Huawei storage R&D engineers to repair the pool.
63.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show storage_pool general command to check the tier's status.
63.0.criterion = If the tier's Health Status is Normal, the tier is normal. Otherwise, it is abnormal.

64.name = Hotspare capacity
64.0.name = Hotspare capacity
64.0.suggestion = 1.  Hotspare Used Capacity equal  to zero is Normal.  \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
64.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show storage_pool tier POOL_ID command
64.0.criterion =  Hotspare Used Capacity equal  to zero is Normal. Otherwise, it is abnormal.

65.name = Extent Migration Status
65.0.name = Extent Migration Status
65.0.suggestion = 1.  It is normal that Relocation Running Status is Readyrelocating or Paused. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
65.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show storage_pool tier POOL_ID command
65.0.criterion =  It is normal that Relocation Running Status is Readyrelocating or Paused. Otherwise, it is an abnormal situation.

66.name = Precopy switch
66.0.name = Precopy switch
66.0.suggestion = 1. It is normal that PreCopy Switch is Enable or Disable. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
66.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show disk precopy command to check the precopy switch. 
66.0.criterion = It is normal that PreCopy Switch is Enable or Disable. Otherwise, it is an abnormal situation.

67.name = BST switch
67.0.name = BST switch
67.0.suggestion = 1. It is normal that the value of Enable is Yes or No. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
67.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the developer command to go to the developer mode. \nStep 3 Run the show bst configuration command to check the bst switch. 
67.0.criterion = It is normal that the value of Enable is Yes or No. Otherwise, it is an abnormal situation.

68.name = LUN Write Policy
68.0.name = LUN Write Policy
68.0.suggestion = 1. It is normal that Write Policy and Running Write Policy have the same value. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
68.0.method = Step 1 Log in to the device as user admin.  \nStep 2 Run the show lun lun_id=LUN_ID command or ignore step 2 and run the show lun |filterRow Write\sPolicy equal_to Write\sback and Running\sWrite\sPolicy not equal_to Write\sback and show lun |filterRow Write\sPolicy equal_to Write\sthrough and Running\sWrite\sPolicy not equal_to Write\sthrough command
68.0.criterion = It is normal that Write Policy and Running Write Policy have the same value. Otherwise, it is an abnormal situation.

69.name = LUN Owning Controllerr
69.0.name = LUN Owning Controllerr
69.0.suggestion = 1. It is normal that Owner Controllerr and Work Controller have the same value. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
69.0.method = Step 1 Log in to the device as user admin.  \nStep 2 Run the show lun lun_id=LUN_ID command or ignore step 2 and run the show lun |filterRow Owner\sController equal_to A and Work\sController not equal_to A and show lun |filterRow Owner\sController equal_to B and Work\sController not equal_to B command
69.0.criterion = It is normal that Owner Controllerr and Work Controller have the same value. Otherwise, it is an abnormal situation.

81.name = Remote replication status
81.0.name = Remote replication status
81.0.suggestion = 1. A remote replication is normal when its Health Status is Normal. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
81.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show remote_replication general command to check the remote replication's status.
81.0.criterion = If the remote replication's Health Status is Normal, the remote replication is normal. Otherwise, it is abnormal.

82.name = Replication link status
82.0.name = Replication link status
82.0.suggestion = 1. A replication link is normal when its Health Status is Normal. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
82.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show remote_device link command to check the replication link's status.
82.0.criterion = If the replication link's Health Status is Normal, the replication link is normal. Otherwise, it is abnormal.

83.name = Virtual snapshot health status
83.0.name = Virtual snapshot health status
83.0.suggestion = 1. A virtual snapshot is normal when its Health Status is Normal. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
83.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show snapshot general command to check the virtual snapshot's health status.
83.0.criterion = If the virtual snapshot's Health Status is Normal, the virtual snapshot is normal. Otherwise, it is abnormal.

84.name = LUN copy health status
84.0.name = LUN copy health status
84.0.suggestion = 1. A LUN copy is normal when its Health Status is Normal. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
84.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show snapshot general command to check the LUN copy's health status.
84.0.criterion = If the LUN copy's Health Status is Normal, the LUN copy is normal. Otherwise, it is abnormal.

85.name = Split mirror health status
85.0.name = Split mirror health status
85.0.suggestion = 1. A split mirror is normal when its Health Status is Normal. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
85.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show mirror general command to check the split mirror's health status.
85.0.criterion = If the split mirror's Health Status is Normal, the split mirror is normal. Otherwise, it is abnormal.

86.name = Consistency group health status
86.0.name = Consistency group health status
86.0.suggestion = 1. Consistency group is normal when its Health Status is Normal. \n.2. If you have any questions, contact Huawei storage R&D engineers for technical support.
86.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show consistency_group general to check the split mirror's health status.
86.0.criterion = If the split mirror's Health Status is Normal, the split mirror is normal. Otherwise, it is abnormal.

91.name = Critical alarm
91.0.name = Critical alarm
91.0.suggestion = 1. It is normal that there are no alarms whose Level is Critical. \n2. If you have any questions, contact Huawei storage R&D engineers for technical support.
91.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show alert command or show alarm level=critical number=10 command to check for critical alarms.
91.0.criterion = It is normal that there are no alarms whose Level is Critical. Otherwise, it is an abnormal situation.

92.name = Major alarm
92.0.name = Major alarm
92.0.suggestion = 1. It is normal that there are no alarms whose Level is Major. \n2. If you have any questions, contact Huawei storage R&D engineers for technical support.
92.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show alert command or show alarm level=major number=10 command to check for major alarms.
92.0.criterion = It is normal that there are no alarms whose Level is Major. Otherwise, it is an abnormal situation.

93.name = Warning alarm
93.0.name = Warning alarm
93.0.suggestion = 1. It is normal that there are no alarms whose Level is Warning. \n2. If you have any questions, contact Huawei storage R&D engineers for technical support.
93.0.method = Step 1 Log in to the device as user admin. \nStep 2 Run the show alarm command or show alarm level=warning number=10 command to check for warning alarms.
93.0.criterion = It is normal that there are no alarms whose Level is Warning. Otherwise, it is an abnormal situation.