A processor over-temperature has been detected. Check for any
environmental issues before replacing any parts.
Is the ambient room temperature in the normal operating range (less
than 35 degrees C/95 degrees F)?
No:
Notify the customer. The customer must bring the room temperature down
so that it is within the normal range. Do not replace any parts. This
ends the procedure.
Yes: Continue to next step.
Are the front and rear of the CEC drawer, and the front and rear
rack doors, free of obstructions that would impede the airflow through the
drawer?
No:
Notify the customer. The system must be free of obstructions for proper
airflow. Clean the air inlets and exits in the drawer as required. Do not
replace any parts. This ends the procedure.
Yes:
Continue to next step.
Are all of the fans, especially those at the back
of the power supply, functioning normally?
No:
Replace any fans that are not turning or are turning slowly. Refer to Locating FRUs for instructions. This ends the procedure.
Yes:
There are no environmental issues with the cooling of the processors.
This ends the procedure.