INTIP08

Use this procedure to ensure that the system is electrically grounded correctly.

  1. Have an installation planning representative or an electrician (when necessary), perform the following steps.
  2. Power off the server and the power network branch circuits before performing this procedure.
  3. Ensure the safety of personnel by making sure that all electrical wiring in the United States meets National Electrical Code requirements.
  4. Check all system receptacles to ensure that each one is wired correctly. This includes receptacles for the server and all equipment that attaches to the server, including workstations. Do this to determine if a wire with primary voltage on it is swapped with the ground wire, causing an electrical shock hazard.
  5. For each unit, check continuity from a conductive area on the frame to the ground pin on the plug. Do this at the end of the mainline ac power cable. The resistance must be 0.1 ohm or less.
  6. Ground continuity must be present from each unit receptacle to an effective ground. Therefore, check the following:
  7. Look inside all power panels to ensure the following:
  8. For systems with more than one unit, ensure that the ground wire for each unit is not connected from one receptacle to the next in a string. Each unit must have its own ground wire, which goes to the power source.
  9. Ensure that the grounding wires are insulated with green (or green and yellow) wire at least equal in size to the phase wires. The grounding wires also should be as short as possible.
  10. If extension-mainline power cables or multiple-outlet power strips are used, make sure that they must have a three-wire cable. One of the wires must be a ground conductor. The ground connector on the plug must not be removed. This applies to any extension mainline power cables or multiple-outlet power strips that are used on the server. It also applies for attaching devices such as personal computers, workstations, and modems.
    Note:
    Check all extension-mainline power cables and multiple-outlet power strips with an ECOS tester and with power that is applied. Ensure that no wires are crossed (for example, a ground wire crossed with a wire that has voltage on it).
    This ends the procedure.