PWR1907

A unit was dropped from the SPCN configuration.

  1. Is the reference code you are working with 1xxx 913B?
    1. Access the advanced system management interface (ASMI) and select System Configuration and then Configure I/O Enclosures.
    2. Record the current SPCN Firmware Update Policy setting so it can be restored later.
    3. Change the SPCN Firmware Update Policy setting to Expanded and click on Save Policy Setting to allow SPCN firmware updates to be done over the RIO/HSL and serial SPCN interfaces.
    4. Select Start SPCN Firmware Update. The SPCN firmware will now be downloaded to the expansion units that require an update.
    5. Change the SPCN Firmware Update Policy setting back to what it was originally set to in step 1b and click on Save Policy Setting.
      Note:
      The SPCN firmware update can be stopped using the Stop SPCN Firmware Update button. However, to allow the expansion units to be updated to the latest SPCN firmware level, it is recommended that the firmware update be allowed to complete.

      The progress of the SPCN firmware update can be monitored by clicking on Configure I/O Enclosures to update the screen. Do not use the browser Back or Refresh button to monitor the update progress. The Power Control Network Firmware Update Status column shows the percentage complete and In Progress is displayed while the download is progresses. Not Required is displayed when the download process completes.

    This ends the procedure.
  2. Is the reference code you are working with 1xxx 90F0?
  3. Using the HMC or ASMI, find the 1xxx 90F0 SRC in the error log (see Displaying error and event logs). Use the Show details option to display the location information for the failing unit.
  4. After locating the failing unit, ensure that the SPCN frame-to-frame cable and RIO cables are seated correctly; reseat the cables if necessary.

    Are the cables connected correctly?

  5. Are the ac line cords on the failing unit connected properly at both ends?
  6. Check the voltage at the customer's ac outlet. Is the voltage correct?
  7. Are the power supplies functional?
  8. Use the table below to determine the FRUs to replace. Refer toLocating FRUs for instructions on replacing FRUs.This ends the procedure.
    Table 30.
    Enclosure FRU
    5088, 0588 Tower backplane assembly
    5094, 5294, 8094-002 Tower backplane assembly
    5095, 0595 Tower backplane assembly
    7311-D11, 7314-G30, 5790 or 5796 I/O backplane
    7311-D20 I/O backplane