PWR1911

You are here because of a power problem on a dual line cord system. If the failing unit does not have a dual line cord, return to the procedure that sent you here or go to the next item in the FRU list.

The following steps are for the system unit, unless other instructions are given. Please refer to Power isolation procedures for important safety information before servicing the system.

  1. If an uninterruptible power supply is installed, verify that it is powered on before proceeding.
  2. Are all the units powered on?
  3. Are you working on a model 9117-MMA, 5095, 0595, 5790, 5796, 7314-G30, 7311-D11, or 7311-D20 ?
  4. Perform the following:
    1. Reconnect the ac line cord to the ac modules.
    2. Remove the ac jumper cables at the power supplies.
    3. Use a multimeter to measure the ac voltage at the jumper cable power supply end.

    Is the ac voltage from 200V to 240V?

  5. Perform the following:
    1. Disconnect the ac jumper cable at the ac module output.
    2. Use a multimeter to measure the ac voltage at the ac module output.

    Is the ac voltage from 200V to 240V?

  6. Perform the following:
    1. Disconnect the ac line cords from the customer's ac power outlet.
    2. Use a multimeter to measure the ac voltage at the customer's ac power outlet.

    Is the ac voltage correct (refer to Table 31)?

  7. Is the reference code 1xxx-00AC?
  8. Is the reference code 1xxx-1510 or 1520?
  9. Is the reference code 1xxx 1500 or 1xxx 1530?
  10. Perform the following:
    1. For the reference code you are working on, disconnect either the ac jumper cable or the ac line cord from the power supply.
    2. Use a multimeter to measure the ac voltage at the power supply end of the ac jumper cable or the ac line cord.

    Is the ac voltage correct (see Table 31)?

  11. Perform the following:
    1. Disconnect the ac line cords from the power outlet.
    2. Use a multimeter to measure the ac voltage at the customer's ac power outlet.

    Is the ac voltage correct (see Table 31)?