PWR1912

The server detected an error in the power system.

DANGER
When working on or around the system, observe the following precautions:

Electrical voltage and current from power, telephone, and communication cables are hazardous. To avoid a shock hazard:

  1. Perform the following:
    1. Ensure that both power line cords are properly connected.
    2. Make sure that the unit EPO switch is in the on position.
    3. Make sure that the unit EPO bypass switches on both bulk power controllers (BPCs) are in the normal position.
    4. Ensure that the cable from unit EPO connector J00 to BPC-A connector J05 and the cable from unit EPO connector J01 to BPC-B connector J05 are secure and undamaged.
    5. Ensure that the room temperature is not in excess of the maximum allowed (40° Celsius or 104° Fahrenheit).
      Note:
      If the room temperature has exceeded the maximum allowed, the system may continually cycle on and off.

    Were any problems discovered while performing the above checks?

  2. Make sure that the on/off switches on all the bulk power regulators (BPRs) are in the on (left) position.
    Note:
    A switch set to the off position is not the cause of your problem, but they all need to be on before proceeding.
  3. Check the state of the LEDs on both sides of the bulk power assembly (BPA) and then choose from the following conditions:
  4. Prepare a voltage meter to measure up to 600 V ac. Using the labelled test points on the frame, measure the voltage between phase A and phase B. Is the voltage greater than 180 V ac?
  5. Is a cable connected to connector J02 on the unit EPO card?
  6. Is the internal toggle switch on the unit EPO card set to the RM EPO BYPASS position?
  7. Unplug the cable from connector J02 on the EPO card and set the toggle switch to the RM EPO BYPASS position. Does the EPO CMPLT LED on at least one BPC become lit?