FSPSP38

The system has detected an error within the JTAG path.

Replace all FRUs explicitly called out, if any, in the service processor error log entry first before continuing in this procedure. Skip those FRUs that have already been replaced during this service call. If one or more of those FRUs fixes the problem, this ends the procedure.
Note: In the "Priority" field in the FRU list, "replace these as a group" may appear even though only one FRU is listed. If that is the case, "replace as a group" can be ignored.

Refer to System FRU locations for information on locating FRUs called out by this procedure.

If the FRU(s) that have been replaced so far have not corrected the problem, perform the following:

Select the system that you are servicing and then perform the indicated FSPSP29 procedure.

8203-E4A, 9407-M15, and 9408-M25
8204-E8A and 9409-M50
8234-EMA, 9117-MMA, and 9406-MMA
9125-F2A
9119-FHA

8203-E4A, 9407-M15, and 9408-M25

  1. Was the FRU called out before this procedure a memory DIMM (Un-P1-C14 through Un-P1-C17 or Un-P1-C21 through Un-P1-C24) or a GX adapter card (Un-P1-C8 or Un-P1-C6)?
    No:
    This ends the procedure
    Yes:
    Continue with 2.
  2. Replace the system backplane (Un-P1).
  3. Perform a slow boot. To review the "Performing a slow boot" procedure go to Performing a slow boot . This ends the procedure.
8204–E8A and 9409-M50
  1. Was the FRU called out before this procedure a memory DIMM (Un-P1-C13-Cx or Un-P1-C14-Cx or Un-P1-C15-Cx or Un-P1-C16-Cx)?
    No:
    Go to step 4.
    Yes:
    Continue with the next step.
  2. Perform the following:
    1. Replace the processor card (Un-P1-C13 or Un-P1-C14 or Un-P1-C15 or Un-P1-C16) that the DIMM was plugged to.
    2. Perform a slow boot. See Performing a slow boot .
    3. Does the problem persist?
      No:
      This ends the procedure
      Yes:
      Continue with the next step.
  3. Perform the following:
    1. Replace the system backplane (Un-P1).
    2. Perform a slow boot. To review the "Performing a slow boot" procedure go to Performing a slow boot . This ends the procedure.
  4. Was the FRU called out before this procedure a processor card (Un-P1-C13 or Un-P1-C14 or Un-P1-C15 or Un-P1-C16) or GX adapter card (Un-P1-C8 or Un-C1-C7)?
    No:
    This ends the procedure.
    Yes:
    Continue with the next step.
  5. Perform the following:
    1. Replace the system backplane (Un-P1).
    2. Perform a slow boot. See Performing a slow boot . This ends the procedure.
8234-EMA, 9117-MMA, and 9406-MMA
  1. Has a Memory DIMM (Un-P2-C1-Cx or Un-P2-C2-Cx) been replaced?
    No:
    Go to step 10.
    Yes:
    A Memory DIMM attention line has an error. Continue to the next step.
  2. Replace the service processor (Un-P1-C11) in the same drawer as the Memory DIMM.
  3. Perform a slow boot. To review the "Performing a slow boot" procedure go to Performing a slow boot .
  4. Does the problem persist?
    No:
    This ends the procedure.
    Yes:
    Continue to the next step.
  5. Replace the processor card (Un-P2-C1 or Un-P2-C2) on which a DIMM has been replaced.
  6. Perform a slow boot. See Performing a slow boot .
  7. Does the problem persist?
    No:
    This ends the procedure.
    Yes:
    Continue with the next step.
  8. Replace the system backplane (Un-P1) in the same drawer as the Memory DIMM.
  9. Perform a slow boot. See Performing a slow boot . This ends the procedure.
  10. Has a processor card (Un-P2-C1 or Un-P2-C2) or GX adapter card (Un-P1-C8 or Un-P1-C9) been replaced?
    No:
    Go to step 16
    Yes:
    A processor card or GX adapter card attention line has an error. Continue to the next step.
  11. Replace the service processor (Un-P1-C11) from the same drawer as the processor card or GX adapter card.
  12. Perform a slow boot. See Performing a slow boot .
  13. Does the problem persist?
    No:
    This ends the procedure.
    Yes:
    Continue with the next step.
  14. Replace the system backplane (Un-P1) from the same drawer as the processor card or GX adapter card.
  15. Perform a slow boot. This ends the procedure.
  16. Was the system backplane (Un-P1) explicitly called out as a FRU before starting step 1 of this procedure?
    No:
    Contact your next level of support. This ends the procedure.
    Yes:
    A P5IOC2 attention line has an error. Continue to the next step.
  17. Replace the service processor (Un-P1-C11) from the same drawer as the system backplane.
  18. Perform a slow boot. See Performing a slow boot . This ends the procedure.
9125-F2A
  1. Was the FRU called out before this procedure a GX adapter card (Un-Pm-Cx, where m = 2 - 9 and x = 37 - 40)?
    No:
    This ends the procedure.
    Yes:
    Continue to the next step.
  2. Replace both node FSP cards (Un-Pm-C41 and Un-Pm-C42, where m = 2 - 9) from the same Node as the GX adapter card.
  3. Perform a slow boot. To review the "Performing a slow boot" procedure go to Performing a slow boot .
  4. Does the problem persist?
    No:
    This ends the procedure.
    Yes:
    Continue to the next step.
  5. Replace the processor book (Un-Pm, where m = 2 - 9) the GX adapter card plugged into.
  6. Perform a slow boot. See Performing a slow boot .This ends the procedure.

9119-FHA

This procedure is not applicable to the 9119–FHA