Emergency power-off shutdown

The SAN Volume Controller and each uninterruptible power supply support emergency power-off (EPO) shutdowns.

In the event of a room EPO shutdown, the 2145 UPS detects a loss of input power. This power loss is reported to the SAN Volume Controller 2145-4F2, which completes the process of shutting down the uninterruptible power supply within five minutes.

Attention: The 2145 UPS power off shutdown is normally controlled by the SAN Volume Controller 2145-4F2. If an EPO event occurs, but no SAN Volume Controller 2145-4F2 nodes that are connected to a 2145 UPS have been powered on since the 2145 UPS was powered on, you must remove output power from the uninterruptible power supply. To do this, press and hold the off button on the front panel of the 2145 UPS for at least four seconds.