Explanation
The output load on the 2145 UPS-1U exceeds the specifications (reported by 2145 UPS-1U alarm bits).
Action
- Ensure that only 2145s are receiving power from the
uninterruptible power supply. Also, ensure that no other devices are connected to the 2145 UPS-1U.
- Exchange, in the sequence shown, the FRUs for new FRUs. See "Possible Cause-FRUs or other"
after the last action in this section. If the Overload Indicator is still illuminated with
all outputs disconnected, replace the 2145 UPS-1U.
- Check node status. If all nodes show a status of "online", mark the error that you have just repaired "fixed".
If any nodes do not show a status of "online", go to start MAP. If you return
to this step, contact your support center to resolve the problem with the 2145 UPS-1U.
- Go to repair verification MAP.
Possible Cause-FRUs or other:
- Power cable assembly (50%)
- Power supply assembly (40%)
- 2145 UPS-1U assembly (10%)