Explanation
The 2145 detected that the current of the 2145 UPS exceeds the current that four 2145s require.
Action
- Ensure also that only 2145s are receiving power from the 2145 UPS; that is, no switches or disk controllers are connected to the 2145 UPS.
- If only one 2145 is connected to the 2145 UPS, exchange the FRU for a new FRU. See "Possible Cause-FRU or other." If more than one 2145 is connected to the 2145 UPS, disconnect the 2145s from the 2145 UPS and reconnect them one-at-a-time. While the problem persists, the nodes fail to start with boot error code 215 displayed on the 2145 front panel. When the first failure occurs, exchange the FRU for a new FRU. See "Possible Cause-FRU or other."
Possible Cause-FRUs or other:
- 2145 UPS electronics assembly (40%)
- 2145 power supply assembly (10%)
- Other: Configuration error (50%)