Explanation
The ambient temperature threshold for the 2145 UPS-1U has been exceeded.
Action
- Turn off the 2145 UPS-1U and unplug it from the power source.
- Clear the vents and remove any heat sources.
- Ensure that the air flow around the 2145 UPS-1U is not restricted.
- Wait at least five minutes, and then restart the 2145 UPS-1U.
- If the problem remains, exchange, in the sequence shown, the FRUs for new FRUs. (See "Possible Cause-FRUs or other.")
Possible Cause-FRUs or other:
- 2145 UPS-1U assembly (100%)