Before the SAN Volume Controller 2145-4F2 is installed, the physical environment must meet certain requirements. This includes verifying that adequate space is available and that requirements for power and environmental conditions are met. The SAN Volume Controller 2145-4F2 node is supported only in SAN Volume Controller 4.3.1 and earlier releases.
Ensure that your environment meets the following voltage requirements.
| Voltage | Frequency |
|---|---|
| 200 to 240 V single phase ac | 50 or 60 Hz |
Ensure that your environment meets the following power requirements.
The power that is required depends on the node type and whether the redundant ac power feature is used.
| Components | Power requirements |
|---|---|
| SAN Volume Controller 2145-4F2 and 2145 UPS-1U | 420 W |
| One SAN Volume Controller 2145-4F2 and one 2145 UPS | 760 W |
| Two SAN Volume Controller 2145-4F2 nodes and one 2145 UPS | 1120 W |
For each redundant ac-power switch, add 20 W to the power requirements.
Ensure that your environment falls within the following ranges if you are not using redundant ac power.
| Environment | Temperature | Altitude | Relative humidity | Maximum wet bulb temperature |
|---|---|---|---|---|
| Operating in lower altitudes | 10°C to 35°C (50°F to 95°F) |
0 to 914.4 m (0 to 3000 ft) |
8% to 80% noncondensing | 23°C (74°F) |
| Operating in higher altitudes | 10°C to 32°C (50°F to 88°F) |
914.4 to 2133.6 m (3000 to 7000 ft) |
8% to 80% noncondensing | 23°C (74°F) |
| Turned off | 10°C to 43°C (50°F to 110°F) |
0 to 2133.6 m (0 to 7000 ft) |
8% to 80% noncondensing | 27°C (81°F) |
| Storing | 1°C to 60°C (34°F to 140°F) |
0 to 2133.6 m (0 to 7000 ft) |
5% to 80% noncondensing | 29°C (84°F) |
| Shipping | -20°C to 60°C (-4°F to 140°F) |
0 to 10668 m (0 to 34991 ft) |
5% to 100% condensing, but no precipitation | 29°C (84°F) |
Ensure that your environment falls within the following ranges if you are using redundant ac power.
| Environment | Temperature | Altitude | Relative humidity | Maximum wet bulb temperature |
|---|---|---|---|---|
| Operating in lower altitudes | 15°C to 32°C (59°F to 89°F) |
0 to 914.4 m (0 to 3000 ft) |
20% to 80% noncondensing | 23°C (74°F) |
| Operating in higher altitudes | 15°C to 32°C (50°F to 88°F) |
914.4 to 2133.6 m (3000 to 7000 ft) |
20% to 80% noncondensing | 23°C (74°F) |
| Turned off | 10°C to 43°C (50°F to 110°F) |
0 to 2133.6 m (0 to 7000 ft) |
20% to 80% noncondensing | 27°C (81°F) |
| Storing | 1°C to 60°C (34°F to 140°F) |
0 to 2133.6 m (0 to 7000 ft) |
5% to 80% noncondensing | 29°C (84°F) |
| Shipping | -20°C to 60°C (-4°F to 140°F) |
0 to 10668 m (0 to 34991 ft) |
5% to 100% condensing, but no precipitation | 29°C (84°F) |
The following tables list the physical characteristics of the SAN Volume Controller 2145-4F2 node.
Ensure that space is available in a rack that is capable of supporting the node.
| Height | Width | Depth | Maximum weight |
|---|---|---|---|
43 mm |
440 mm |
686 mm |
12.7 kg |
Ensure that space is also available in the rack for the following additional space requirements around the node.
| Location | Additional space |
Reason |
|---|---|---|
| Left and right sides | 50 mm (2 in.) |
Cooling air flow |
| Back | Minimum: |
Cable exit |
The node dissipates the following maximum heat output.
| Model | Heat output per node |
|---|---|
| SAN Volume Controller 2145-4F2 | 350 W (1200 Btu per hour) |