Installing the SAN Volume Controller 2145-8G4 cable retention bracket

The cable retention bracket ensures that the SAN Volume Controller 2145-8G4 node does not mistakenly become unplugged from the uninterruptible power supply.

The SAN Volume Controller 2145-8G4 comes with a cable retention bracket that attaches to the back of the node. The cable retention bracket is connected with the screws that already hold the rear plate of the power supply in place.
Figure 1. SAN Volume Controller 2145-8G4 cable retention bracket - type ASAN Volume Controller 2145-8G4 cable retention bracket option A

Install the SAN Volume Controller 2145-8G4 cable retention bracket after you install the node in the rack.

To attach the bracket, perform the following steps:
  1. With the node powered off and the power cable removed, unscrew and remove the two screws reference key one on the right side of the rear plate that covers the power supply fan unit, as shown in Figure 3.
    Figure 2. The SAN Volume Controller 2145-8G4 before you attach the cable-retention bracketThis photo shows the SAN Volume Controller 2145-8G4 before the cable-retention bracket is attached.
  2. Insert the power cable.
  3. Position the cable retention bracket so that the power cable runs through the slot in the bracket, as shown in Figure 3. Align the screw holes in the bracket with the holes that are in the rear plate where you removed the two screws.
  4. Replace the top screw.
  5. Move the power supply handle back into place over the retention bracket, and replace the lower screw so that it holds the power supply handle, cable retention bracket, and power supply rear plate in place.
    Figure 3. The SAN Volume Controller 2145-8G4 with the cable-retention bracket attachedthis photo shows the SAN Volume Controller 2145-8G4 with the cable-retention bracket attached.