Connect the SAN Volume Controller to
the 2145 UPS-1U to
protect your data in the event of an unexpected loss of external power.
Notes: - To make the SAN Volume Controller cluster
more resilient to power failure, the 2145 UPS-1U units
can be connected to the redundant ac-power switch.
If a redundant ac-power switch is
not used, you can connect the two uninterruptible
power supply units
that are powering an I/O group to different, independent electrical
power sources. If a single power source fails, the SAN Volume Controller cluster
can then continue to operate with reduced performance.
- When connecting to the 2145 UPS-1U,
use only the power cable assembly, part number 31P1177, that was supplied
with the node. Power cable assemblies that were supplied with previous SAN Volume Controller models
do not work with the 2145-8A4 model.
The correct part is differentiated by the red tape that is used to
bind the cables together.
Before you begin this task, see the completed
customer's cable-connection table, which is described in the IBM® System Storage® SAN Volume Controller
Planning Guide and
can be downloaded from www.ibm.com/storage/support/2145.
Use the information in this table to identify
the 2145 UPS-1U unit
to which this node is to be connected.
Perform
the following steps to connect the SAN Volume Controller to
the 2145 UPS-1U:
- At the back of the SAN Volume Controller 2145-8A4 node,
plug the power cable of the combined power and serial cable into the
power connector 1 , as shown in Figure 1.
Figure 1. Connecting the SAN Volume Controller 2145-8A4 power
cable to the 2145 UPS-1U
- 1 Power connector
- 2 Serial connector
- 3 Main power connector
- 4 Communication port
- 5 Load segment 2 receptacle
- Place the other end of the power cable into the rightmost
load segment 2 receptacle 5 on the 2145 UPS-1U.
DANGER
You
have already switched on the 2145 UPS-1U.
The output sockets of the 2145 UPS-1U are
live.
- Plug the signal cable into the serial connector 2 located
on the SAN Volume Controller 2145-8A4 node.
- Place the other end of the signal cable into the communication
port 4 on the 2145 UPS-1U.
The SAN Volume Controller 2145-8A4 power
is now connected to the 2145 UPS-1U.