All controls and indicators for the 2145 UPS-1U are located on the front-panel assembly.
| 1 Load2 | 2 Load1 | 3 Alarm | 4 Battery | 5 Overload | 6 Power-on | Buzzer | Error condition |
|---|---|---|---|---|---|---|---|
| Green (see Note 1) | Green | (see Note 3) | No errors; the 2145 UPS-1U was configured by the SAN Volume Controller | ||||
| Green | Amber (see Note 2) | Green | No errors; the 2145 UPS-1U is not yet configured by the SAN Volume Controller | ||||
| Green | Either on or off | Amber | Green | Beeps for two seconds and then stops | The ac power is over or under limit. The uninterruptible power supply has switched to battery mode. | ||
| Flashing red | Flashing amber | Flashing red | Flashing green | Three beeps every ten seconds | Battery undervoltage | ||
| Green | Either on or off | Flashing red | Flashing green | Solid on | Battery overvoltage | ||
| Flashing red | Flashing amber | Flashing green | Solid on | Output wave is abnormal when the charger is open, on battery mode | |||
| Flashing red | Flashing amber | Solid on | The ac-power output wave is under low limit or above high limit on battery mode | ||||
| Green | Either on or off | Amber | Beeps for four seconds and then stops | On battery (no ac power) | |||
| Green | Either on or off | Flashing amber | Beeps for two seconds and then stops | Low battery (no ac power) | |||
| Green | Either on or off | Red | Green | Beeps for one second and then stops | Overload while on line | ||
| Amber | Red | Beeps for one second and then stops | Overload while on battery | ||||
| Either on or off | Either on or off | Flashing red | Green | Solid on | Fan failure | ||
| Either on or off | Either on or off | Flashing red | Amber | Solid on | Battery test fail | ||
| Flashing red | Red | Solid on | Overload timeout | ||||
| Flashing red | Amber | Green | Solid on | Over temperature | |||
| Flashing red | Amber | Red | Green | Output short circuit | |||
Notes:
|
|||||||