After you have completed the preparation procedures, you
are ready to install the 2145 UPS-1U in
the rack.
Attention: See
Safety and environmental notices before you start the installation
process. Use the reference numbers in parentheses at the end of each
safety notice to find the matching translated notice. For the translation
of the danger, caution, and attention notices,
see the
IBM Systems Safety Notices.
CAUTION:
The uninterruptible
power supply contains
its own energy source (sealed, lead-acid batteries). The output receptacles
might carry live voltage, even when the uninterruptible
power supply is
not connected to an ac supply. (11)
CAUTION:
Do
not remove or unplug the input cord when the uninterruptible
power supply is
turned on. Unplugging the input cord removes the safety ground from
the uninterruptible
power supply and
the equipment connected to the uninterruptible
power supply.
(12)
CAUTION:
To reduce the risk of fire
or electric shock, install the uninterruptible
power supply in
a temperature- and humidity-controlled indoor environment, free of
conductive contaminants. Ambient temperature must not exceed 40°C
(104°F). Do not operate near water or excessive humidity (95% maximum).
(13)
CAUTION:
To
avoid any hazard from the rack tipping forward when devices are installed,
observe all safety precautions for the rack into which you are installing
the device.
Perform the following steps to install the
2145 UPS-1U in
the rack.
Note: You might have already completed steps
3 through
6 if you used the
Read
Me First pamphlet, which is included with the
2145 UPS-1U.
- Stand at the front of the rack and place the back of the 2145 UPS-1U onto
the support rails, and then slide the 2145 UPS-1U into
the rack.
CAUTION:
The 2145 UPS-1U weighs
16 kg (35.3 lb). If you feel unsure about lifting the uninterruptible
power supply to
its location in the rack, seek assistance or remove the battery to
reduce its weight.
- At the front of the 2145 UPS-1U,
install the two mounting screws (M6x10) 1 as
shown in Figure 1.
Figure 1. Mounting screws for the 2145 UPS-1U
- If you have not already connected
the internal battery connector, remove the 2145 UPS-1U front
panel, shown in Figure 2,
by pushing the panel to the left and then pulling it forward.
Figure 2. Removing the 2145 UPS-1U front
panel
- Remove the protective label from the internal battery connector
(shown in Figure 3).
Figure 3. The 2145 UPS-1U internal
battery connector with protective tape
- Connect the internal battery connector (shown in Figure 4). Each end of
the keyed connector has two wires: one red (+) and one black (−).
Align the connector so that the two red wires are joined together
and the two black wires are joined together.
Note: A small
amount of arcing might occur when connecting the batteries. This is
normal and does not damage the unit or present any safety concerns.
Figure 4. The 2145 UPS-1U internal-battery
connector
- Reinstall the front panel. You might first need
to move the sliding section on the front of the 2145 UPS-1U to
the closed position.
- At the back of the 2145 UPS-1U,
plug the 2145 UPS-1U main-power
connector into the power socket.
The
power socket is shown by 1 in Figure 5.
The 2145 UPS-1U is
in standby mode; so all indicators are off.
Connect
each 2145 UPS-1U for
an I/O group to a different power source.
Figure 5. 2145 UPS-1U (rear
view)
- 1 Main power connector
- 2 Communication port
- 3 Load segment
2 receptacles
Attention: Ensure that you comply with the following
requirements:
- The voltage supplied to the 2145 UPS-1U must
be 200 - 240 V single phase.
- The frequency supplied must be 50 or 60 Hz.
Notes: - The 2145 UPS-1U has
an integrated circuit breaker and does not require external protection.
- The 2145 UPS-1U is
intended to maintain power on SAN Volume Controller nodes
until data can be saved to the local hard-disk drive. Only SAN Volume Controller nodes
can be plugged into the 2145 UPS-1U or
the SAN Volume Controller cluster
will malfunction.
- Press and hold the on/off button ( 7 in Figure 6)
for approximately five seconds. You might need a pointed device, such
as a screwdriver, to press the on/off button. The front panel indicators
cycle through a startup sequence while the 2145 UPS-1U conducts
a self-test.
Figure 6. 2145 UPS-1U front-panel
assembly
When the self-test
is complete, the power-on indicator 6 and
the load indicators ( 1 and 2 )
illuminate to indicate that power is being supplied by the 2145 UPS-1U.
The 2145 UPS-1U is
now in normal mode, and is charging its battery. If the battery
indicator 4 is on and the alarm is sounding,
the voltage range setting might not be correct. When a SAN Volume Controller is
connected to the 2145 UPS-1U,
the SAN Volume Controller automatically
adjusts the voltage range setting. Take no action for this alarm
condition unless it persists for more than five minutes after a SAN Volume Controller has
been connected to this 2145 UPS-1U and
turned on.
- Repeat all of these steps to install additional 2145 UPS-1U units.