After you have completed the preparation
procedures, you can install
the 2145 UPS in
the rack.
You
must complete the following prerequisites before
you install the 2145 UPS in
the rack:
- Complete the preinstallation procedures.
- Install
the support rails for the 2145 UPS.
- Prepare your 2145 UPS environment.
Attention: See
Safety and environmental notices before you start the installation
process. Use the reference numbers in parentheses at the end of each
safety notice to find the matching translated notice. For the translation
of the danger, caution, and attention notices,
see the
IBM Systems Safety Notices.
CAUTION:
The uninterruptible
power supply contains
its own energy source (sealed, lead-acid batteries). The output receptacles
might carry live voltage, even when the uninterruptible
power supply is
not connected to an ac supply. (11)
CAUTION:
Do
not remove or unplug the input cord when the uninterruptible
power supply is
turned on. Unplugging the input cord removes the safety ground from
the uninterruptible
power supply and
the equipment connected to the uninterruptible
power supply.
(12)
CAUTION:
To reduce the risk of fire
or electric shock, install the uninterruptible
power supply in
a temperature- and humidity-controlled indoor environment, free of
conductive contaminants. Ambient temperature must not exceed 40°C
(104°F). Do not operate near water or excessive humidity (95% maximum).
(13)
CAUTION:
To
avoid any hazard from the rack tipping forward when devices are installed,
observe all safety precautions for the rack into which you are installing
the device.
The 2145 UPS weighs
39 kg (86 lb) with the electronics assembly and the battery assembly
installed:- Do not attempt to lift the 2145 UPS by
yourself. Ask another service representative for assistance.
- Remove the battery assembly from the 2145 UPS before
removing the 2145 UPS from
the shipping carton.
- Do not attempt to install the 2145 UPS into
the rack unless the electronics assembly and the battery assembly
have been removed.
Perform the following steps to install the 2145 UPS in
the rack:
- Before you remove the 2145 UPS from
the shipping carton, you must reduce its weight by removing the battery
assembly.
Perform the following steps to remove the 2145 UPS battery
assembly:
- Open the top of the 2145 UPS shipping
carton. With the assistance of another service representative, grip
the flaps
on either side of the 2145 UPS,
as shown in Figure 1.
Figure 1. Opening
the top of the 2145 UPS shipping
carton
- Slide
the 2145 UPS to
the end of the carton and rest its front edge on the edge of the carton,
as
shown in Figure 2.
Figure 2. Sliding
the 2145 UPS to
the end of the carton.
- Remove
the two bolts
and additional nut
on the left side of the bracket, as shown
in Figure 3.
Next,
remove the battery retaining bracket
. Figure 3. Fastening
the battery retaining bracket
Bolts
Nut
Battery
retaining bracket
- Grip the
tab on the front of the battery and pull the battery
forward until it can be accessed by two service representatives.
- With the assistance of another service representative,
lift
the battery assembly clear of the 2145 UPS and
place to one side.
Note: The front cover for the 2145 UPS is
not installed, however, it is included inside of the shipping carton.
The
front cover is installed later in the installation process.
- With the assistance of another
service representative, lift the 2145 UPS clear
of the shipping carton and place it on a flat, stable surface.
- Remove the two screws
(shown in Figure 4).
- Pull the electronics assembly
out of the 2145 UPS,
and put it to one side. Figure 4. Removing the 2145 UPS electronics
assembly
Screws
Electronics
assembly
- Stand at the front of
the rack. With the help of another service
representative, place the back of the 2145 UPS onto
the support rails and then slide it into the rack.
- Install the front flathead screws (
in Figure 5). Figure 5. Installing
the 2145 UPS into
a rack
Front
flathead screws
- With the assistance
of another service representative, reinstall
the following parts:
- Battery assembly
- Battery retaining bracket
- Electronics assembly
Attention: A
grounding
screw feature is provided on the back of the 2145 UPS so
that you can attach a ground bonding wire, if it
is required
by local wiring codes. Because safety grounding of the 2145 UPS chassis
is maintained through the input line power cord, you are usually not
required
to use this additional grounding screw feature.
- Install the front panel.
- At the back of the 2145 UPS,
plug the 2145 UPS main
power cable (
in Figure 6)
into
the power socket. Note: The 2145 UPS is
intended to maintain power on SAN
Volume Controller 2145-4F2 nodes
until data can be saved to the local hard
disk drive. Only SAN
Volume Controller 2145-4F2 nodes
can be plugged in to the 2145 UPS,
or the SAN
Volume Controller 2145-4F2 cluster
malfunctions.
Figure 6. Installing
the 2145 UPS power
cable
Main
power cable
If possible, ensure that the two uninterruptible
power supply units
are not both connected to the same power source. Ensure that you comply
with
the following requirements for the 2145 UPS:
- Each 2145 UPS should
be connected to a separate branch circuit.
- A UL-listed 15
A circuit breaker must be installed in each branch circuit
that supplies power to the 2145 UPS.
- The voltage that is supplied to the 2145 UPS must
be 200 – 240 V single phase.
- The frequency that
is supplied must
be 50 or 60 Hz.
Note: If the 2145 UPS is
cascaded from another uninterruptible
power supply,
the source uninterruptible
power supply must
have at least 3 times the capacity per phase and the total harmonic
distortion
must be less than 5%. The uninterruptible
power supply should
also have input voltage capture that has a slew rate of no more than
3 Hz
per second.
- All front panel indicators
of the 2145 UPS flash
for a short time while the 2145 UPS runs
a self-test. When the test is complete, the mode indicator
flashes
to show that the 2145 UPS is
in
standby mode; see Figure 7. Press and hold the 2145 UPS On
button,
in Figure 7,
until
you hear the 2145 UPS beep
(approximately one second). The mode indicator stops flashing and
the load-level
indicators display the percentage of load that is being supplied by
the 2145 UPS.
The 2145 UPS is
now
in normal mode and is charging its battery.
Figure 7. Power
switch and indicators on the 2145 UPS
Mode
indicator
On
button
If the mode indicator
is flashing red and the
alarm is sounding, the voltage range setting
might not be correct. When a SAN
Volume Controller 2145-4F2 is
connected to the 2145 UPS,
the SAN
Volume Controller 2145-4F2 automatically
adjusts the voltage range setting. Take no action for this alarm condition
unless it persists for more than five minutes after a SAN
Volume Controller 2145-4F2 has
been connected to this 2145 UPS and
powered on.
- Repeat all of these steps
to install additional 2145 UPS units.