Before installing a SAN Volume Controller 2145-CF8 node, your physical environment must meet certain requirements. This includes verifying that adequate space is available and that requirements for power and environmental conditions are met.
Ensure that your environment meets the following voltage requirements.
| Voltage | Frequency |
|---|---|
| 200 to 240 V single phase ac | 50 or 60 Hz |
Ensure that your environment meets the following power requirements.
The power capacity that is required depends on the node type and which optional features are installed.
| Components | Power requirements |
|---|---|
| SAN Volume Controller 2145-CF8 node and 2145 UPS-1U power supply | 200 W |
For each redundant ac-power switch, add 20 W to the power requirements.
The 2145 UPS-1U has an integrated circuit breaker and does not require additional protection.
Ensure that your environment falls within the following ranges if you are not using redundant ac power.
| Environment | Temperature | Altitude | Relative humidity | Maximum wet bulb temperature |
|---|---|---|---|---|
| Operating in lower altitudes | 10°C to 35°C (50°F to 95°F) |
0 to 914 m (0 to 2998 ft) |
8% to 80% noncondensing | 23°C (73°F) |
| Operating in higher altitudes | 10°C to 32°C (50°F to 90°F) |
914 to 2133 m (2998 to 6988 ft) |
8% to 80% noncondensing | 23°C (73°F) |
| Turned off | 10°C to 43°C (50°F to 110°F) |
0 to 2133 m (0 to 6988 ft) |
8% to 80% noncondensing | 27°C (81°F) |
| Storing | 1°C to 60°C (34°F to 140°F) |
0 to 2133 m (0 to 6988 ft) |
5% to 80% noncondensing | 29°C (84°F) |
| Shipping | -20°C to 60°C (-4°F to 140°F) |
0 to 10668 m (0 to 34991 ft) |
5% to 100% condensing, but no precipitation | 29°C (84°F) |
Ensure that your environment falls within the following ranges if you are using redundant ac power.
| Environment | Temperature | Altitude | Relative humidity | Maximum wet bulb temperature |
|---|---|---|---|---|
| Operating in lower altitudes | 15°C to 32°C (59°F to 90°F) |
0 to 914 m (0 to 2998 ft) |
20% to 80% noncondensing | 23°C (73°F) |
| Operating in higher altitudes | 15°C to 32°C (59°F to 90°F) |
914 to 2133 m (2998 to 6988 ft) |
20% to 80% noncondensing | 23°C (73°F) |
| Turned off | 10°C to 43°C (50°F to 110°F) |
0 to 2133m (0 to 6988 ft) |
20% to 80% noncondensing | 27°C (81°F) |
| Storing | 1°C to 60°C (34°F to 140°F) |
0 to 2133 m (0 to 6988 ft) |
5% to 80% noncondensing | 29°C (84°F) |
| Shipping | -20°C to 60°C (-4°F to 140°F) |
0 to 10668 m (0 to 34991 ft) |
5% to 100% condensing, but no precipitation | 29°C (84°F) |
The following tables list the physical characteristics of the SAN Volume Controller 2145-CF8 node.
Ensure that space is available in a rack that is capable of supporting the node.
| Height | Width | Depth | Maximum weight |
|---|---|---|---|
43 mm |
440 mm |
686 mm |
12.7 kg |
Ensure that space is also available in the rack for the following additional space requirements around the node.
| Location | Additional space |
Reason |
|---|---|---|
| Left and right sides | 50 mm (2 in.) |
Cooling air flow |
| Back | Minimum: |
Cable exit |
The node dissipates the following maximum heat output.
| Model | Heat output per node |
|---|---|
| SAN Volume Controller 2145-CF8 | 160 W (546 Btu per hour) |
| SAN Volume Controller 2145-CF8 and up to four optional solid-state drives (SSDs) | 210 W (717 Btu per hour) |
| Maximum heat output of 2145 UPS-1U during typical operation: | 10 W (34 Btu per hour) |
| Maximum heat output of 2145 UPS-1U during battery operation: | 100 W (341 Btu per hour) |