Before you remove the 2145 UPS-1U,
read all safety notices.
Use the reference
numbers in parentheses at the end of each notice, such as (C003) for
example, to find the matching translated notice in IBM® Systems Safety Notices.
DANGER
Uninterruptible power
supply units
contain specific hazardous materials. Observe the following precautions
if your product contains an
uninterruptible
power supply:
- The uninterruptible
power supply contains
lethal voltages. All repairs and service must be performed only by
an authorized service support representative. There are no user serviceable
parts inside the uninterruptible
power supply.
- The uninterruptible
power supply contains
its own energy source (batteries). The output receptacles might carry
live voltage even when the uninterruptible
power supply is
not connected to an ac supply.
- Do not remove or unplug the input cord when the uninterruptible
power supply is
turned on. This removes the safety ground from the uninterruptible
power supply and
the equipment connected to the uninterruptible
power supply.
- The uninterruptible
power supply is
heavy because of the electronics and batteries that are required.
To avoid injury, observe the following precautions:
- Do not attempt to lift the uninterruptible
power supply by
yourself. Ask another service representative for assistance.
- Remove the battery, electronics assembly, or both from the uninterruptible
power supply before
removing the uninterruptible
power supply from
the shipping carton or installing or removing the uninterruptible
power supply in
the rack.
(D007)
CAUTION:
This
part or unit is heavy but has a weight smaller than 18 kg (39.7 lb).
Use care when lifting, removing, or installing this part or unit.
(C008)
Perform the following steps to remove the 2145 UPS-1U:
- At the front of the 2145 UPS-1U,
press and hold the on/off button ( 1 in Figure 1) until the power light
is extinguished (approximately five seconds). On some versions of
the 2145 UPS-1U,
you need a pointed device, such as a screwdriver, to press the on/off
button. The 2145 UPS-1U enters
standby mode.
Figure 1. The 2145 UPS-1U front-panel
assembly
- At the back of the 2145 UPS-1U,
remove the power cable retainer before disconnecting the SAN Volume Controller power
cable from load segment receptacle 2 ( 3 in Figure 2).
- Disconnect the signal cable from the communication port
( 2 in Figure 2).
- Disconnect the main power cable from the main power source
( 1 in Figure 2).
Figure 2. 2145 UPS-1U (rear
view)
Some SAN Volume Controller node
types have two power supply units. Both power supplies must be connected
to the same 2145 UPS-1U.
The SAN Volume Controller 2145-CF8 is
an example of a node that has two power supplies. The SAN Volume Controller 2145-8A4 is
an example of a node that has a single power supply.
- Remove the 2145 UPS-1U front
panel, as shown in Figure 3.
Note: If you are having difficulty pulling the right
side of the panel free from the 2145 UPS-1U,
insert a flat-blade screwdriver between the right side of the cover
and the frame and gently pry it free.
Figure 3. Removing the 2145 UPS-1U front
panel
- Disconnect the internal battery connector, which is circled
in Figure 4.
Figure 4. The 2145 UPS-1U internal-battery
connector
- After pulling the two connectors apart, cover the exposed
battery connector (shown in Figure 5)
with adhesive tape.
Figure 5. The 2145 UPS-1U internal
battery connector with protective tape
- Reinstall the front panel.
- At the front of the 2145 UPS-1U,
unscrew the two mounting screws
, as shown in Figure 6. Figure 6. Mounting screws for the 2145 UPS-1U
- From the back of the rack, push the 2145 UPS-1U forward
approximately 5 cm (2 in) to enable you to pull it from the rack.
- Go to the front of the rack.
- Pull the 2145 UPS-1U forward
and remove it from the rack.