This topic describes how to replace the SAN Volume Controller 2145-CF8 top
cover.
Important: Before you slide the cover forward,
make sure that all the tabs on both the front, rear, and side of the
cover engage the chassis correctly. If all the tabs do not engage
the chassis correctly, it will be very difficult to remove the cover
later.
To replace the top cover on the SAN Volume Controller 2145-CF8,
complete the following steps:
- If you removed the node from the rack, replace the node
in the rack, as described in Replacing the SAN Volume Controller in a rack.
- Make sure that all cables, adapters, and other components
are installed and seated correctly and that you have not left loose
tools or parts inside the node. Make sure that all internal cables
are correctly routed. If you disconnected the fibre-channel and Ethernet
cables, make sure that each cable is reconnected to the same port
from which it was removed.
- If you removed
the power cords, replace the power cords and the cable-retention brackets,
as described in Replacing the cable-retention bracket.
- Position the cover on top of the SAN Volume Controller 2145-CF8.
Important: Before you slide the cover forward,
make sure that all the tabs on both the front, rear, and side of the
cover engage the chassis correctly. If all the tabs do not engage
the chassis correctly, it will be very difficult to remove the cover
later.
- Slide the cover toward the front of the node, as shown
in Figure 1.
Figure 1. Replacing the SAN Volume Controller 2145-CF8 cover
- 1 Cover
- 2 Blue locking tab
- Verify that the cover correctly engages all the inset tabs
on the node.
- Lift the locking levers ( 1 in Figure 2)
on the slide rails and push the server 2 all
the way into the rack until it clicks into place.
Figure 2. Raising the SAN Volume Controller 2145-CF8 locking
levers of the slide rails of the rack
- If you turned off the node during the service procedure,
turn on the node.