Follow these instructions when you are prompted to replace
the SAN Volume Controller 2145-8F4 or
the SAN Volume Controller 2145-8F2 in
a rack.
Attention: Do
not touch the power control switches on adjacent SAN Volume Controller nodes
when you remove or install SAN Volume Controller nodes
in a rack. Touching these switches on adjacent SAN Volume Controller nodes
might cause those devices to turn off and make customer data inaccessible.
Perform the following steps to replace the SAN Volume Controller 2145-8F4 or
the SAN Volume Controller 2145-8F2 in
the rack:
- Slide the SAN Volume Controller 2145-8F4 or
the SAN Volume Controller 2145-8F2 node
into the rack.
- Latch the two latches on the front of the rack to attach
the node to the rack. ( 1 in Figure 1).
Note: The front of the rail assembly looks different from the
front, as you can see in
Figure 1.
Figure 1. Sliding the SAN Volume Controller 2145-8F4 into
the rack
- Reconnect the fibre-channel
and Ethernet cables. Ensure that you replace the fibre-channel
and Ethernet cables in the same ports from which they were removed.
- Connect the power cable to the node and replace the
cable-retention bracket. See Replacing the cable-retention bracket.
- Turn on the node.