Follow all safety notices when you are replacing the 2145 UPS-1U battery.
CAUTION:
Lead-acid
batteries can present a risk of electrical burn from high, short-circuit
current. Avoid battery contact with metal materials; remove watches,
rings, or other metal objects, and use tools with insulated handles.
To avoid possible explosion, do not burn.
Exchange only with the
IBM-approved part. Recycle or discard the battery as instructed by
local regulations. In the United States, IBM has a process for the
collection of this battery. For information, call 1-800-426-4333.
Have the IBM part number for the battery unit available when you call.
(C004)
Use the reference
numbers in parentheses at the end of each notice, such as (C003) for
example, to find the matching translated notice in IBM® Systems Safety Notices.
This task assumes that you have disconnected the 2145 UPS-1U battery
and have turned off the SAN Volume Controller.
Perform the following steps to replace the 2145 UPS-1U battery:
- Slide the battery into the 2145 UPS-1U,
as shown in Figure 1.
Figure 1. Replacing the 2145 UPS-1U battery
- Thread the battery connector through the battery cover.
Position the battery cover in place and slide it to the left to secure
it.
- Connect the internal battery connector, as shown in Figure 3. Each end of
the keyed connector has two wires: one red (+) and one black (−).
Join the black wires and the red wires together.
Note: A
small amount of arcing might occur when connecting the batteries.
This is normal and does not damage the unit or present any safety
concerns.
Figure 2. The 2145 UPS-1U internal-battery
connector
- Push the front panel to the right to catch on the left
end of the panel. Push the front panel forward until the panel snaps
into the right and middle sections of the 2145 UPS-1U,
as shown in Figure 3.
Figure 3. Replacing the 2145 UPS-1U front
panel
- Ensure that the 2145 UPS-1U is
turned on. Press and hold the 2145 UPS-1U test
button for three seconds to start the self-test. If any of the Alarm,
Battery, or Overload indicators are on or the buzzer is sounding,
go to MAP 5150: 2145 UPS-1U to
resolve the problem.
Note: Ignore all error indicators
until the self-test has been run.
- Turn on the SAN Volume Controller.
Note: If the new battery does not have enough charge to support
the actions that are required during a power failure, the SAN Volume Controller node
pauses with Charging displayed on its
front panel until a sufficient charge is available. If there is a
sufficient charge to support the actions that are required during
a single power failure but not sufficient charge to support two power
failures, the node starts and joins the cluster but displays Recovering on
its front panel.