Replacing the SAN Volume Controller 2145-4F2 microprocessor fans

Note:
  • The airflow is from the front to the back of the SAN Volume Controller 2145-4F2 node.
  • The fan cable comes out of the back of the fan. When you install the fan, ensure that the back of the fan is facing the back of the node.
  • If you are installing a microprocessor fan, orient the fan in the retaining clip so that the cable can reach the connector on the system board.

Perform the following steps to replace the microprocessor fan:

  1. Push the fan downward into the retaining clip. Figure 1 shows the location of the fans and the retaining clips.
    Figure 1. SAN Volume Controller 2145-4F2 microprocessor fan locations
    This figure shows the location of the SAN Volume Controller 2145-4F2 microprocessor fans
  2. Connect the fan cable to the system board.
    Note: The fans are numbered from one to four, from left to right.
  3. Replace the top cover. See Replacing the top cover.
  4. Place the node in the rack. See Replacing the SAN Volume Controller in a rack.
  5. Turn on the node.