The SAN Volume Controller 2145-8F4 or SAN Volume Controller 2145-8F2 power
backplane might have to be replaced.
Take
precautions to avoid damage from static electricity. Wear an anti-static
wrist strap and use a static-protected mat or surface. For more information,
see Handling static-sensitive devices.
Perform the following steps to replace the power backplane:
- Lower the power backplane into position on the SAN Volume Controller 2145-8F4 or SAN Volume Controller 2145-8F2 and
slide it to the right to connect it to the system board. See Figure 1.
Figure 1. Replacing the SAN Volume Controller 2145-8F4 or SAN Volume Controller 2145-8F2 power
backplane
- Connect the power supply to the power backplane.
- Replace
the top cover. See Replacing the top cover.
- Place the node in the
rack. See Replacing the SAN Volume Controller in a rack.
- Reconnect the fibre-channel
and Ethernet cables. Ensure that you replace the fibre-channel
and Ethernet cables in the same ports from which they were removed.
- Turn on the node.