Replacing the SAN Volume Controller 2145-8F4 or SAN Volume Controller 2145-8F2 power backplane

The SAN Volume Controller 2145-8F4 or SAN Volume Controller 2145-8F2 power backplane might have to be replaced.

Take precautions to avoid damage from static electricity. Wear an anti-static wrist strap and use a static-protected mat or surface. For more information, see Handling static-sensitive devices.
Perform the following steps to replace the power backplane:
  1. Lower the power backplane into position on the SAN Volume Controller 2145-8F4 or SAN Volume Controller 2145-8F2 and slide it to the right to connect it to the system board. See Figure 1.
    Figure 1. Replacing the SAN Volume Controller 2145-8F4 or SAN Volume Controller 2145-8F2 power backplaneReplacing the SAN Volume Controller 2145-8F4 or SAN Volume Controller 2145-8F2 power backplane
  2. Connect the power supply to the power backplane.
  3. Replace the top cover. See Replacing the top cover.
  4. Place the node in the rack. See Replacing the SAN Volume Controller in a rack.
  5. Reconnect the fibre-channel and Ethernet cables. Ensure that you replace the fibre-channel and Ethernet cables in the same ports from which they were removed.
  6. Turn on the node.