Replacing the SAN Volume Controller 2145-8G4 cable retention bracket

The SAN Volume Controller 2145-8G4 uses one of two different cable-retention brackets. Depending on which bracket you have, use the appropriate instructions to remove and replace the cable-retention bracket.

Replacing the cable-retention bracket - option A

The cable-retention bracket attaches to the back of the SAN Volume Controller 2145-8G4 node. It is connected with the screws that already hold the rear plate of the power supply in place.

Replace the SAN Volume Controller 2145-8G4 cable retention bracket after you replace the node in the rack.

To attach the bracket to the rack rail, perform the following steps:
  1. With the node powered off and the power cable removed, loosen and remove the two screws reference key one on the right side of the rear plate that covers the power supply fan unit, as shown in Figure 3.
    Figure 3. The SAN Volume Controller 2145-8G4 before you attach the cable-retention bracketThis photo shows the SAN Volume Controller 2145-8G4 before the cable-retention bracket is attached.
  2. Rotate the power supply handle out of the way.
  3. Insert the power cable.
  4. Position the cable-retention bracket so that the power cable runs through the slot in the bracket. Align the screw holes in the bracket with the holes that are in the rear plate where you removed the two screws.
  5. Replace the top screw.
  6. Move the power supply handle back into place over the retention bracket, and replace the lower screw so that it holds the power supply handle, cable-retention bracket, and power supply rear plate in place.

Replacing the cable-retention bracket - option B

Replace the SAN Volume Controller 2145-8G4 cable retention bracket after you replace the node in the rack.

Install the SAN Volume Controller 2145-8G4 cable retention bracket after you install the node in the rack.

To attach the bracket to the rack rail, perform the following steps:
  1. Install the power cable into the power supply.
  2. At the back of the cabinet, remove the securing bolt from the node side rail next to the power supply, as shown in Figure 4.
    Figure 4. The SAN Volume Controller 2145-8G4 with cable-retention bracket type B attachedThis figure shows the SAN Volume Controller 2145-8G4 with cable-retention bracket type B attached.
  3. Slide the cable-retention bracket over the cable and position it over the side rail. Secure it in place using the original bolt.