Replacing the SAN Volume Controller 2145-8A4 operator-information panel cable

Use these instructions when you are prompted to replace the operator-information panel cable for the SAN Volume Controller 2145-8A4.

Perform the following steps to replace the operator-information panel cable:
  1. Connect the two connectors at one end of the operator-information panel cable assembly to the Front USB connector Reference key one and the Operator-information panel connector Reference key two on the system board. The connectors are keyed and it is important to insert the correct connector on the cable assembly onto the correct connector on the system board.
    Figure 1. Connectors for the operator-information panel on the SAN Volume Controller 2145-8A4 system boardThis figure shows the connectors for the operator-information panel on the SAN Volume Controller 2145-8A4 system board
    • reference key one Front USB connector
    • reference key two Operator-information panel connector
  2. Route the operator-information panel cable into position along the same path that it was removed from:
    1. Pass to the right of the mounting bracket for the rightmost fan (when viewed from the front of the node and ignoring the fan on the power supply).
    2. Go between the fans and the disk drive back plate, under the cable retention-clip, and around the processor fans to the left side of the node.
    3. Bring it forward to the operator-information panel.
  3. Use a tie-wrap to hold the cable assembly to the lower right front corner of the mounting bracket for the rightmost fan.
  4. Connect the two connectors on the other end of the cable to the connectors on the operator-information panel board. The connectors are keyed and it is important to insert the correct connector on the cable onto the correct connector on the operator-information panel board.
  5. If the back plate was removed, replace the back plate, disk drive, and service controller. See Removing the disk-drive backplane.
  6. Rotate the air deflector back into place, making sure not to pinch any cables beneath it, and press it down firmly. Ensure that any other cable that was unplugged or moved is returned to its original position and does not obstruct the top cover of the node.
  7. Replace the top cover. See Replacing the top cover.
  8. Place the node in the rack. See Replacing the SAN Volume Controller in a rack.
  9. Connect the power cable to the node and replace the cable-retention bracket. See Replacing the cable-retention bracket.