MAP 5150: 2145 UPS-1U

MAP 5150: 2145 UPS-1U helps you solve problems that have occurred in the 2145 UPS-1U systems that are used on a SAN Volume Controller.

If you are not familiar with these maintenance analysis procedures (MAPs), first read Using the maintenance analysis procedures.

You may have been sent here for one of the following reasons:
  • The system problem determination procedures sent you here
  • A problem occurred during the installation of a SAN Volume Controller
  • Another MAP sent you here
  • A customer observed a problem that was not detected by the system problem determination procedures
Figure 1 shows an illustration of the front of the panel for the 2145 UPS-1U.
Figure 1. 2145 UPS-1U front-panel assembly
This figure shows the 2145 UPS-1U front-panel assembly.
  • Reference key number one identifies the power-on indicator. Load segment 2 indicator
  • Reference key number two identifies the on/off button. Load segment 1 indicator
  • Reference key number three identifies the test and alarm reset button. Alarm
  • Reference key number four identifies the overload indicator. On-battery indicator
  • Reference key number five identifies the on-battery indicator. Overload indicator
  • Reference key number six identifies the service indicator. Power-on indicator
  • Reference key number seven identifies the load segment 1 indicator. On/off button
  • Reference key number eight identifies the load segment 2 indicator. Test and alarm reset button
Table 1 identifies which status and error LEDs that display on the 2145 UPS-1U front-panel assembly relate to the specified error conditions. It also lists the uninterruptible power supply alert-buzzer behavior.
Table 1. 2145 UPS-1U error indicators
 1  Load2  2  Load1  3  Alarm  4  Battery  5  Overload  6  Power-on Buzzer Error condition
Green (see Note 1)         Green (see Note 3) No errors; the 2145 UPS-1U was configured by the SAN Volume Controller
Green Amber (see Note 2)       Green   No errors; the 2145 UPS-1U is not yet configured by the SAN Volume Controller
Green Either on or off   Amber   Green Beeps for two seconds and then stops The ac power is over or under limit. The uninterruptible power supply has switched to battery mode.
    Flashing red Flashing amber Flashing red Flashing green Three beeps every ten seconds Battery undervoltage
Green Either on or off Flashing red     Flashing green Solid on Battery overvoltage
    Flashing red Flashing amber   Flashing green Solid on Output wave is abnormal when the charger is open, on battery mode
    Flashing red Flashing amber     Solid on The ac-power output wave is under low limit or above high limit on battery mode
Green Either on or off   Amber     Beeps for four seconds and then stops On battery (no ac power)
Green Either on or off   Flashing amber     Beeps for two seconds and then stops Low battery (no ac power)
Green Either on or off     Red Green Beeps for one second and then stops Overload while on line
      Amber Red   Beeps for one second and then stops Overload while on battery
Either on or off Either on or off Flashing red     Green Solid on Fan failure
Either on or off Either on or off Flashing red Amber     Solid on Battery test fail
    Flashing red   Red   Solid on Overload timeout
    Flashing red Amber   Green Solid on Over temperature
    Flashing red Amber Red Green   Output short circuit
Notes:
  1. The green Load2 LED ( 1 ) indicates that power is being supplied to the right pair of ac-power outlets as seen from the rear of the 2145 UPS-1U.
  2. The amber Load1 LED ( 2 ) indicates that power is being supplied to the left pair of ac-power outlets as seen from the rear of the 2145 UPS-1U. These outlets are not used by the SAN Volume Controller.

    This LED might be illuminated during power-on sequences, but it is typically extinguished by the SAN Volume Controller node that is attached to the 2145 UPS-1U.

  3. A blank cell indicates that the light or buzzer is off.
  1. Is the power-on indicator for the 2145 UPS-1U that is connected to the failing SAN Volume Controller off?
    NO
    Go to step 3.
    YES
    Go to step 2.
  2. (from step 1)
    Are other 2145 UPS-1U units showing the power-on indicator as off?
    NO
    The 2145 UPS-1U might be in standby mode. This can be because the on/off button on this 2145 UPS-1U was pressed, input power has been missing for more than five minutes, or because the SAN Volume Controller shut it down following a reported loss of input power. Press and hold the on/off button until the 2145 UPS-1U power-on indicator is illuminated (approximately five seconds). On some versions of the 2145 UPS-1U, you need a pointed device, such as a screwdriver, to press the on/off button.

    Go to step 3.

    YES
    Either main power is missing from the installation or a redundant ac-power switch has failed. If the 2145 UPS-1U units are connected to a redundant ac-power switch, go to MAP 5320: Redundant ac power. Otherwise, complete these steps:
    1. Restore main power to installation.
    2. Verify the repair by continuing with MAP 5250: 2145 UPS-1U repair verification.
  3. (from step 1 and step 2)
    Are the power-on and load segment 2 indicators for the 2145 UPS-1U illuminated solid green, with service, on-battery, and overload indicators off?
    NO
    Go to step 4.
    YES
    The 2145 UPS-1U is no longer showing a fault. Verify the repair by continuing with MAP 5250: 2145 UPS-1U repair verification.
  4. (from step 3)
    Is the 2145 UPS-1U on-battery indicator illuminated yellow (solid or flashing), with service and overload indicators off?
    NO
    Go to step 5.
    YES
    The input power supply to this 2145 UPS-1U is not working or is not correctly connected, or the 2145 UPS-1U is receiving input power that might be unstable or outside the specified voltage or frequency range. (The voltage should be between 200V and 240V and the frequency should be either 50 Hz or 60 Hz.) The SAN Volume Controller automatically adjusts the 2145 UPS-1U voltage range. If the input voltage has recently changed, the alarm condition might be present until the SAN Volume Controller has adjusted the alarm setting. Power on the SAN Volume Controller that is connected to the 2145 UPS-1U. If the SAN Volume Controller starts the on-battery indicator should go off within five minutes. If the SAN Volume Controller powers off again or if the condition persists for at least five minutes, do the following:
    1. Check the input circuit protector on the 2145 UPS-1U rear panel, and press it, if it is open.
    2. If redundant ac power is used for the 2145 UPS-1U, check the voltage and frequency at the redundant ac-power switch output receptable connected to this 2145 UPS-1U. If there is no power, go to MAP 5340: Redundant ac power verification. If the power is not within specification, ask the customer to resolve the issue. If redundant ac power is not used for this uninterruptible power supply, check the site power outlet for the 2145 UPS-1U providing power to this SAN Volume Controller. Check the connection, voltage, and frequency. If the power is not within specification, ask the customer to resolve the issue.
    3. If the input power is within specification and the input circuit protector is stable, replace the field-replaceable units (FRUs) in the following sequence:
      1. 2145 UPS-1U power cord
      2. 2145 UPS-1U
    4. Verify the repair by continuing with MAP 5250: 2145 UPS-1U repair verification.
  5. (from step 4)
    Is the 2145 UPS-1U overload indicator illuminated solid red?
    NO
    Go to step 6.
    YES
    The 2145 UPS-1U output power requirement has exceeded the 2145 UPS-1U capacity.
    1. Check that only one SAN Volume Controller node is connected to the 2145 UPS-1U.
    2. Check that no other loads are connected to the 2145 UPS-1U.
    3. After ensuring that the output loading is correct, turn off the 2145 UPS-1U by pressing the on/off button until the power-on indicator goes off. Then unplug the input power from the 2145 UPS-1U. Wait at least five seconds until all LEDs are off and restart the 2145 UPS-1U by reconnecting it to input power and pressing the on/off button until the 2145 UPS-1U power-on indicator is illuminated (approximately five seconds). On some versions of the 2145 UPS-1U, you need a pointed device, such as a screwdriver, to press the on/off button.
    4. If the condition persists, replace the 2145 UPS-1U.
      Note: If the condition recurs, replace the power supply or power supplies in the node. See Replacing the power supply.
    5. Verify the repair by continuing with MAP 5250: 2145 UPS-1U repair verification.
  6. (from step 5)
    Is the 2145 UPS-1U service indicator illuminated flashing red and the on-battery indicator illuminated solid yellow, with the power-on and overload indicators off?
    NO
    Go to step 7.
    YES
    The 2145 UPS-1U battery might be fully discharged or faulty.
    1. Check that the 2145 UPS-1U has been connected to a power outlet for at least two hours to charge the battery. After charging the battery, press and hold the test/alarm reset button for three seconds; and then check the service indicator.
    2. If the service indicator is still flashing, replace the 2145 UPS-1U.
    3. Verify the repair by continuing with MAP 5250: 2145 UPS-1U repair verification.
  7. (from step 6)
    Is the 2145 UPS-1U service indicator illuminated flashing red, the on-battery indicator illuminated solid yellow, and the power-on illuminated solid green, with the overload indicator off?
    NO
    Go to step 8.
    YES
    The 2145 UPS-1U internal temperature is too high.
    1. Turn off turn off the 2145 UPS-1U by pressing the on/off button until the power-on indicator goes off. Then unplug the 2145 UPS-1U. Clear vents at the front and rear of the 2145 UPS-1U. Remove any heat sources. Ensure the airflow around the 2145 UPS-1U is not restricted.
    2. Wait at least five minutes and restart the 2145 UPS-1U by reconnecting to input power and pressing the on/off button until the 2145 UPS-1U power-on indicator is illuminated (approximately five seconds).
    3. If the condition persists, replace the 2145 UPS-1U.
    4. Verify the repair by continuing with MAP 5250: 2145 UPS-1U repair verification.
  8. (from step 7)
    Is the 2145 UPS-1U, service, on-battery, overload, and power-on indicators illuminated and flashing?
    NO
    The 2145 UPS-1U has an internal fault.
    1. Replace the 2145 UPS-1U.
    2. Verify the repair by continuing with MAP 5250: 2145 UPS-1U repair verification.
    YES
    The 2145 UPS-1U battery might be fully discharged or faulty.
    1. Check that the 2145 UPS-1U has been connected to a power outlet for at least two hours to charge the battery. After charging the battery, press and hold the test/alarm reset button for three seconds and then check the service indicator.
    2. If the service indicator is still flashing, replace the 2145 UPS-1U.
    3. Verify the repair by continuing with MAP 5250: 2145 UPS-1U repair verification.