2145 UPS environment

Ensure that your physical site meets the installation requirements of the 2145 UPS.

Uninterruptible power supply specifications

The following tables describe the physical characteristics of the 2145 UPS.

Attention: Ensure that you comply with the following requirements for the 2145 UPS units:
  • If the uninterruptible power supply is cascaded from another uninterruptible power supply, the source uninterruptible power supply must have at least three times the capacity per phase and the total harmonic distortion must be less than 5%.
  • The uninterruptible power supply must also have input voltage capture that has a slew rate of no more than 3 Hz per second.

2145 UPS dimensions and weight

Ensure that space is available in a rack that is capable of supporting the 2145 UPS.
Height Width Depth Maximum weight

89 mm (3.5 in.)

483 mm (19 in.)

622 mm (24.5 in.)

37 kg (84 lb)

Heat output

The 2145 UPS unit produces the following approximate heat output.

Model Heat output during normal operation Heat output during battery operation
2145 UPS powering two SAN Volume Controller 2145-4F2 nodes 140 W (480 Btu per hour) 250 W (850 Btu per hour)