MAP 5200: 2145 UPS helps
you solve problems that have occurred in the 2145 UPS systems
used on a SAN
Volume Controller 2145-4F2.
If you are not familiar with these maintenance analysis
procedures (MAPs), first read Using the maintenance analysis procedures.
You
might have been sent here for one of the following reasons:
- The system problem determination procedures sent you here
- A problem occurred during the installation of a SAN
Volume Controller 2145-4F2
- Another MAP sent you here
- A customer observed a problem that was not detected by the system
problem determination procedures
- Is the mode indicator for the 2145 UPS that
is connected to the failing SAN
Volume Controller 2145-4F2 off?
- NO
- Go to step 3.
- YES
- Go to step 2.
- (from step 1)
Are other 2145 UPS units
showing the mode indicator off?- NO
- The power supply to this 2145 UPS is
faulty or not connected correctly.
- Ask the customer to check the site power connection to this 2145 UPS.
- If the input power connection is stable, replace the field-replaceable units (FRUs) in
the following sequence:
- 2145 UPS power
cord
- 2145 UPS electronics
assembly
- 2145 UPS assembly
- Verify the repair by continuing with MAP 5300: 2145 UPS repair verification.
- YES
- Main power is missing from installation.
- Restore main power to installation.
- Verify the repair by continuing with MAP 5300: 2145 UPS repair verification.
- (from step 1)
Is the 2145 UPS mode
indicator illuminated and flashing green?- NO
- Go to step 4.
- YES
- The 2145 UPS is
in standby mode. This can be because the SAN
Volume Controller 2145-4F2 nodes
powered by this 2145 UPS have
been turned off for more than five minutes, or the off button on this 2145 UPS was
pressed.
- Press and hold the on button until you hear the 2145 UPS beep
(approximately one second) and the power-on indicator shows solid
green. If the mode indicator does not change to solid green, replace
the 2145 UPS electronics
assembly.
- Verify the repair by continuing with MAP 5300: 2145 UPS repair verification.
- (from step 3)
Is the mode indicator illuminated solid red?- NO
- Go to step 8.
- YES
- The 2145 UPS is
in bypass mode. Go to step 5
- (from step 4)
Is the 2145 UPS overload
load level indicator illuminated red?- NO
- Go to step 6.
- YES
- The 2145 UPS output
power requirement exceeded the 2145 UPS capacity.
- Check that no more than two SAN
Volume Controller 2145-4F2 nodes
are connected to the 2145 UPS.
- Check that only SAN
Volume Controller 2145-4F2 nodes
are connected to the 2145 UPS.
- After ensuring output loading is correct, turn off and unplug
the input power from the 2145 UPS.
Wait at least five seconds until all LEDs are off and restart the 2145 UPS by
reconnecting to input power and pressing the on button until you hear
the 2145 UPS beep
(approximately one second).
- If the condition persists, call the IBM® Support
Center.
- Verify the repair by continuing with MAP 5300: 2145 UPS repair verification.
- (from step 5)
Is the 2145 UPS general
alarm indicator illuminated and flashing red (causing a continuous
audible alarm)?- NO
- Go to step 7.
- YES
- The 2145 UPS internal
temperature is too high.
- Turn off and unplug the 2145 UPS.
Clear the vents at the front and rear of the 2145 UPS.
Remove any heat sources. Ensure the airflow around the 2145 UPS is
not restricted.
- Wait at least five minutes and restart the 2145 UPS by
reconnecting to input power and pressing the on button until you hear
the 2145 UPS beep
(approximately one second).
- If the condition persists, replace the 2145 UPS electronics
assembly.
- Verify the repair by continuing with MAP 5300: 2145 UPS repair verification.
- (from step 6)
Is the 2145 UPS Battery
Mode indicator illuminated and flashing red (causing an audible beep
every five seconds)?- NO
- The 2145 UPS is
in bypass mode because of an internal 2145 UPS fault.
- Replace the following assemblies in turn:
- 2145 UPS electronics
assembly
- 2145 UPS battery
assembly
- 2145 UPS assembly
- Verify the repair by continuing with MAP 5300: 2145 UPS repair verification.
- YES
- The 2145 UPS battery
might be fully discharged or not connected correctly.
- Check that the 2145 UPS battery
assembly is installed correctly.
- Check that the 2145 UPS has
been connected to a power outlet for at least two hours to charge
the battery. After charging the battery, press and hold the test/alarm
reset button for three seconds; and then check the battery mode indicator.
- If the battery mode indicator is still on, replace the 2145 UPS battery
assembly.
- Verify the repair by continuing with MAP 5300: 2145 UPS repair verification.
- (from step 4
Is the 2145 UPS wiring
fault indicator illuminated and flashing red (causing an audible beep
every five seconds)?- NO
- Go to step 9.
- YES
- The 2145 UPS ground
wire connection does not exist or the power input line and neutral
wires are reversed.
- Check the grounding of the 2145 UPS.
- Ask the customer to check the 2145 UPS input
power connection.
- Verify the repair by continuing with MAP 5300: 2145 UPS repair verification.
- (from step 8)
Is the 2145 UPS mode
indicator flashing red (causing an audible beep every five seconds)?
- NO
- Go to step 10.
- YES
- The 2145 UPS is
receiving input power that might be unstable or outside the specified
voltage or frequency range. The SAN
Volume Controller 2145-4F2 automatically
adjusts the 2145 UPS voltage
range. If the input voltage has recently changed, the alarm condition
might be present until the SAN
Volume Controller 2145-4F2 has
adjusted the alarm setting. Ensure that an operational SAN
Volume Controller 2145-4F2 is
connected to the 2145 UPS.
If the condition persists for at least five minutes, do the following:
- Ask the customer to check the site power for the 2145 UPS that
is providing power to this SAN
Volume Controller 2145-4F2.
Check the connection, voltage, and frequency.
- If input power is available, replace the 2145 UPS electronics
assembly.
- Verify the repair by continuing with MAP 5300: 2145 UPS repair verification.
- (from step 9)
Are the 2145 UPS general
alarm, battery power, battery mode, wiring fault, and mode indicators
illuminated and flashing red (causing a continuous audible alarm)?- NO
- The 2145 UPS is
no longer showing a fault. Verify the repair by continuing with MAP 5300: 2145 UPS repair verification.
- YES
- The 2145 UPS is
reporting a fault condition.
- Replace the following assemblies in turn:
- 2145 UPS electronics
assembly
- 2145 UPS battery
assembly
- 2145 UPS assembly
- Verify the repair by continuing with MAP 5300: 2145 UPS repair verification2145 UPS.