MAP 5300: 2145 UPS repair
verification helps you to verify that field-replaceable units (FRUs) that
you have exchanged for new FRUs or repair actions that have been done
have solved all the problems on the SAN Volume Controller 2145 UPS.
If you are not familiar with these maintenance analysis
procedures (MAPs), first read Using the maintenance analysis procedures.
You
might have been sent here because you have performed a repair and
want to confirm that no other problems exist on the machine.
Attention: If a SAN
Volume Controller 2145-4F2 is
turned off for more than five minutes
and it is the only SAN
Volume Controller 2145-4F2 that
is connected to this 2145 UPS,
the 2145 UPS also
powers off. To turn on the 2145 UPS,
press and hold the on button until you hear the 2145 UPS beep
(approximately one second) and the mode indicator shows solid green.
Perform the following steps to verify your repair to the 2145 UPS:
- Is the mode indicator for the repaired 2145 UPS illuminated
solid green and the Load level indicators showing an output load level
between 25% and 100%?
- (from step 1)
Are
all SAN
Volume Controller 2145-4F2 nodes
powered by repaired 2145 UPS powered
on?- NO
- Turn on the power
to all the SAN
Volume Controller 2145-4F2 nodes
that are turned off. Go to step 3.
- YES
- Go to step 3.
- (from step 2)
Are
any nodes still not turned on or showing error codes on the front-panel
display?- NO
- Go to step 4.
- YES
- Continue with MAP 5000: Start.
- (from step 3)
Do SAN
Volume Controller 2145-4F2 nodes
show "charging" on the front
panel display?- NO
- Go to step 5.
- YES
- Wait for the charging display to finish.
(This might
take up to two hours). Go to step 5.
- (from step 4)
Press
and hold the test/alarm reset button on the repaired 2145 UPS for
three seconds to initiate a self-test. During the test, individual
indicators illuminate as various parts of the 2145 UPS are
checked.