Input voltage requirements

When you plan for the power requirements of the DS6000™, consider the input voltage requirements.

Table 1 provides the input voltages and frequencies that the DS6000 storage units support. Inputs are balanced three phase.

Note: The DS6000 storage unit can support voltages that range from 200 V ac to 480 V ac nominal (180 V ac to 508 V ac).
Table 1. DS6000 input voltages and frequencies
Characteristic Low Voltage (Feature 9090) High voltage feature (Feature 9091)
Nominal input voltages 200, 208, 220, or 240 RMS V ac 380, 400, 415, or 480 RMS V ac
Minimum input voltage 180 RMS V ac 333 RMS V ac
Maximum input voltage 264 RMS V ac 508 RMS V ac
Nominal input current (3-ph) 30 Amps 15 Amps
Customer wall breaker rating (3-ph) 50 - 60 Amps 30 Amps
Steady-state input frequencies 50 ± 3 or 60 ± 3.0 Hz 50 ± 3 or 60 ± 3.0 Hz
PLD input frequencies (<10 seconds) 50 ± 3 or 60 ± 3.0 Hz 50 ± 3 or 60 ± 3.0 Hz