Service clearance requirements

The service clearance area is the area around the storage unit that IBM service representatives need to service the unit.

For DS6000™ models, IBM services representatives must open the front and rear covers to service the unit. Use the following minimum service clearances. (These dimensions are also shown on Figure 1.)
  • For the front of the unit, allow a minimum of 121.9 cm (48 in.) for the service clearance.
  • For the rear of the unit, allow a minimum of 76.2 cm (30 in.) for the service clearance.
  • For the sides of the unit, allow a minimum of 5.1 cm (2 in.) for the service clearance.
Figure 1. Service clearance requirements
The required service clearance in the front and back of an individual unit.

Unlike weight distribution areas that are required to handle floor loading, keep in mind that service clearances of adjacent unrelated storage units can overlap.

Note: The terms service clearance and weight distribution area are often confused with each other. The service clearance is the area that is required to open the service covers and to pull out components for servicing. The weight distribution area is the area that is required to distribute the weight of the storage unit.