The service clearance area is the area around the storage unit
that IBM service representatives need to service the unit.
For
DS6000™ models,
IBM services representatives must open the front and rear covers to service
the unit. Use the following minimum service clearances. (These dimensions
are also shown on
Figure 1.)
- For the front of the unit, allow a minimum of 121.9 cm (48 in.) for the
service clearance.
- For the rear of the unit, allow a minimum of 76.2 cm (30 in.) for the
service clearance.
- For the sides of the unit, allow a minimum of 5.1 cm (2 in.) for the service
clearance.
Figure 1. Service clearance requirements
Unlike weight distribution areas that are required to handle
floor loading, keep in mind that service clearances of adjacent unrelated
storage units can overlap.
Note: The terms service clearance and weight
distribution area are often confused with each other. The service clearance
is the area that is required to open the service covers and to pull out components
for servicing. The weight distribution area is the area that is required to
distribute the weight of the storage unit.