Powered on

Plan for the DS6000™ operating ranges and recommended operating points when the storage unit is on.

Table 1 provides the operating ranges for your storage unit when the power is on.
Table 1. Operating extremes with the power on
Altitude 0 - 2133 m (0 - 7000 ft)
Dry bulb temperature 16 - 32°C (60 - 90°F)
Relative humidity 20 - 80%
Wet bulb temperature (maximum) 23°C (73°F)
Table 2 provides the operating points that IBM® recommends for your storage unit with the power on.
Table 2. Recommended operating points with the power on
Temperature 22°C (72°F)
Relative humidity 45%
Table 3 provides the operating ranges that IBM recommends for a storage unit with the power on.
Table 3. Recommended operating ranges with the power on
Temperature 20 - 25°C (68 - 77°F)
Relative humidity 40 - 50%