For each DS6000™ series model or expansion unit, service personnel must be able to open the front and rear covers to perform service.
Service clearance refers to the empty space in front of, next to, or behind a storage unit that a service person needs in order to access the unit. The service clearance of adjacent units can overlap. Weight distribution areas that are required to handle floor loading do not overlap.
Use the following minimum service clearances as you plan the placement of your system.