1 Introduction
This document provides instructions on how to install the Certified HW for Cloud Execution Environment (CEE).
1.1 Scope
This document describes installation of the CEE, version 1.1 HP c7000, with three enclosures and a total of 48 blades.
2 Prerequisites
This section describes the prerequisites which must be fulfilled before installation work begins.
2.1 Safety
Ericsson safety instruction Personal Health and Safety Information and System Safety Information must be studied thoroughly and practiced throughout the installation.
For safety practices used when working with power equipment, see Safety Rules for Work with Power, Climate and Energy-Supervision Equipment, Reference [1].
2.2 Documents
Before starting this procedure, ensure that the following documents have been read and understood:
Before starting this procedure, ensure that the following information or documents are available:
- Information about product name, platform, Bill of Material (BOM), work order, and part list.
- Site Information Documentation, with information about:
- Floor layout including the position of the cabinet to be installed.
- Floor plan specification.
- Grounding Information.
- Cabinet allocation specification.
- Cabinet allocation drawing determining each units location in the cabinet with front, back, and side views.
- Cabling Information providing information about all connections needed.
2.3 Tools
The following tools are needed:
- Tools in accordance with cabinet supplier instructions
- Torx screwdriver, T25 × 75 - 200 mm
- Torx screwdriver, T30 × 75 - 200 mm
- Torque wrench 1/4 inch, 10 Nm with T25 × 75 mm and T30 × 75 mm Torx bits
- Tools for tie-wraps
- Equipment for handling pallets and cabinets
2.4 Equipment
Lifting equipment for HP enclosure, with a lifting capacity of at least 250 kg.
2.5 Conditions
The site and location is prepared and the installation space is marked.
Keys and access are available.
All work related to transport, installation, commissioning, and maintenance must be carried out by qualified personnel according to IEC 60364, European standard HD 384 and national work safety regulations.
2.6 Site Requirements
This section lists the space requirements for the site where the cabinet is to be installed.
The equipment is heavy. Lifting the equipment without the aid of a lifting device can cause injury.
- Note:
- The equipment is heavy. Consider if the floor needs to be reinforced to be able to carry the heavy equipment.
Cabinet Requirements
Standard 19-inch equipment rack, following IEC 60 297 or IEC 60 917, for example, Ericsson BYB504.
- Width: 48.3 cm (19 inches)
- Minimum Depth: 106.5 cm (41.9 inches)
- Height: at least space for 15 U
Floor Planning Requirements.
To enable efficient servicing, the recommended clearance around the cabinet is 120 cm (47.2 inches).
To enable normal servicing and to ensure adequate airflow, observe the following minimum spatial requirements when deciding where to install a cabinet:
- Leave a minimum clearance of 120 cm (47.2 inches) in front of the cabinet.
- Leave a minimum clearance of 80 cm (31.5 inches) in back of the cabinet.
- Leave a minimum clearance of 120 cm (47.2 inches) from the back of the cabinet to the rear of another cabinet or row of cabinets.
- Room height from top of floor to ceiling: 310 cm (122 inches or 10 feet, and 2 inches).
Power Requirements
The AC power must be protected from surges, dips, and interruptions. The protection can be implemented by using a Uninterrupted Power Supply (UPS) and a Surge Protector. If a UPS is used, the battery capacity must be sufficient to sustain system operation during short AC power failures and until the servers have been shut down properly to minimize the risk of system faults or data corruption.
Power is best managed within the rack by the use of one or more rack-mounted Power Distribution Units (PDUs). Depending on the configuration, it can be necessary to use multiple PDUs to connect all devices inside the rack. If possible, supply power from different sources and phases for a redundant power supply.
Site power distribution design and installation are not covered in document. Factors related to power distribution and installation must be considered in the site preparation process.
An example of AC power distribution is shown in the following table.
|
Supply |
Fuse |
Unit |
Port |
Power Cord and |
|---|---|---|---|---|
|
AC, Phase 1, Group A |
16 A |
HP C7000 Enclosure 0 |
Power Supply Bay 1 |
IEC 320 C19-C20 |
|
AC, Phase 2, Group A |
16 A |
HP C7000 Enclosure 0 |
Power Supply Bay 2 |
IEC 320 C19-C20 |
|
AC, Phase 3, Group A |
16 A |
HP C7000 Enclosure 0 |
Power Supply Bay 3 |
IEC 320 C19-C20 |
|
AC, Phase 1, Group B |
16 A |
HP C7000 Enclosure 0 |
Power Supply Bay 4 |
IEC 320 C19-C20 |
|
AC, Phase 2, Group B |
16 A |
HP C7000 Enclosure 0 |
Power Supply Bay 5 |
IEC 320 C19-C20 |
|
AC, Phase 3, Group B |
16 A |
HP C7000 Enclosure 0 |
Power Supply Bay 6 |
IEC 320 C19-C20 |
|
AC, Phase 2, Group A |
16 A |
HP C7000 Enclosure 1 |
Power Supply Bay 1 |
IEC 320 C19-C20 |
|
AC, Phase 3, Group A |
16 A |
HP C7000 Enclosure 1 |
Power Supply Bay 2 |
IEC 320 C19-C20 |
|
AC, Phase 1, Group A |
16 A |
HP C7000 Enclosure 1 |
Power Supply Bay 3 |
IEC 320 C19-C20 |
|
AC, Phase 2, Group B |
16 A |
HP C7000 Enclosure 1 |
Power Supply Bay 4 |
IEC 320 C19-C20 |
|
AC, Phase 3, Group B |
16 A |
HP C7000 Enclosure 1 |
Power Supply Bay 5 |
IEC 320 C19-C20 |
|
AC, Phase 1, Group B |
16 A |
HP C7000 Enclosure 1 |
Power Supply Bay 6 |
IEC 320 C19-C20 |
|
AC, Phase 3, Group A |
16 A |
HP C7000 Enclosure 2 |
Power Supply Bay 1 |
IEC 320 C19-C20 |
|
AC, Phase 1, Group A |
16 A |
HP C7000 Enclosure 2 |
Power Supply Bay 2 |
IEC 320 C19-C20 |
|
AC, Phase 2, Group A |
16 A |
HP C7000 Enclosure 2 |
Power Supply Bay 3 |
IEC 320 C19-C20 |
|
AC, Phase 3, Group B |
16 A |
HP C7000 Enclosure 2 |
Power Supply Bay 4 |
IEC 320 C19-C20 |
|
AC, Phase 1, Group B |
16 A |
HP C7000 Enclosure 2 |
Power Supply Bay 5 |
IEC 320 C19-C20 |
|
AC, Phase 2, Group B |
16 A |
HP C7000 Enclosure 2 |
Power Supply Bay 6 |
IEC 320 C19-C20 |
|
AC, Phase 1, Group A |
10 A |
EMC VNX5400 |
PS A |
IEC 320 C13 |
|
AC, Phase 1, Group B |
10 A |
EMC VNX5400 |
PS B |
IEC 320 C13 |
|
AC, Phase 2, Group A |
10 A |
Extreme 770 Switch |
PSU A |
IEC 320 C13 |
|
AC, Phase 2, Group B |
10 A |
Extreme 770 Switch |
PSU B |
IEC 320 C13 |
|
AC, Phase 3, Group A |
10 A |
Extreme 770 Switch |
PSU A |
IEC 320 C13 |
|
AC, Phase 3, Group B |
10 A |
Extreme 770 Switch |
PSU B |
IEC 320 C13 |
|
AC, Phase 1, Group A |
10 A |
Extreme 770 Switch |
PSU A |
IEC 320 C13 |
|
AC, Phase 1, Group B |
10 A |
Extreme 770 Switch |
PSU B |
IEC 320 C13 |
|
AC, Phase 2, Group A |
10 A |
Extreme 770 Switch |
PSU A |
IEC 320 C13 |
|
AC, Phase 2, Group B |
10 A |
Extreme 770 Switch |
PSU B |
IEC 320 C13 |
|
AC, Phase 3, Group A |
10 A |
Extreme 460 |
PSU A |
IEC 320 C13 |
|
AC, Phase 3, Group B |
10 A |
Extreme 460 |
PSU B |
IEC 320 C13 |
|
AC, Phase 1, Group A |
10 A |
Extreme 460 |
PSU A |
IEC 320 C13 |
|
AC, Phase 1, Group B |
10 A |
Extreme 460 |
PSU B |
IEC 320 C13 |
- Note:
- The relevant National regulations apply to all work carried out. Electrical installation must be carried out according to the relevant regulations with regards to cable cross sections, fuse, and Protective grounding.
3 Overview
This section provides an overview of the installation process and the hardware configuration
3.1 Concept for Installing CEE HW
This section describes the concept and process of installing the HP c7000 hardware for Cloud Execution Environment HW.
The system is modular and built up by using one or several enclosures, hosting a number of HP BL460 Gen9 blades. The maximum number of blades in each enclosure is 16. This instruction describes how to assemble the enclosures and units in each cabinet and how to interconnect the units. Each enclosure is built in similar ways while the number of units and the interconnections depends on the configuration. In this document, the configurations described contain fully equipped enclosures, while the product structure can contain variations down to the number of blades used.
The flow of installation contains the following steps on a high level:
- Install Cabinets
- Install HP enclosures, storage units, and switch units
- Install small form-factor pluggable units
- Connect power cables
- Connect control cables
- Connect traffic and storage cables
- Connect the Northbound Interfaces to Border Gateway (BGw), Firewall (FW), and external cables
3.2 Certified Configuration
The certified configuration is shown in the following table:
|
Certified Configuration Components: |
Quantity |
|---|---|
|
Enclosures (HP c7000) |
3 |
|
Blades (HP BL 460) |
48 |
|
Extreme X460 switches. |
2 |
|
Extreme X770 switches. |
4 |
|
EMC VNX5400 |
1 |
4 Preparing the Installation
4.1 Unpacking and Checking the Material
Follow the instructions from the suppliers on how to unpack the equipment.
Verify that:
- The delivery is complete according to documentation.
- All boxes are free from damages.
- The content of the boxes, the delivered equipment, is undamaged and complete according to documentation of parts.
Report all deviations to the implementation project.
- Note:
- Handle the optical cables with care to prevent damage. Never bend the optical cables sharper than the manufacturer's specified minimum bend radius. Never bend the optical cables near a connector strain relief boot, nor over a sharp edge. Bundle the optical cables loosely using cable straps.
5 Installing Cabinets
5.1 Moving and Handling the Cabinet
See applicable section in cabinet installation Instructions.
At least two persons are required.
The equipment is heavy. Lifting the equipment without the aid of a lifting device can cause injury.
5.2 Mechanical Installation
See applicable section in cabinet installation Instructions.
Install tip protection.
Attach cabinets together.
Secure the cabinets in earthquake areas.
5.3 Grounding the Cabinet
See applicable section in cabinet installation instructions.
Connect a grounding cable between cabinets, if necessary.
5.4 Connecting Power
Improper electrical installation may cause fire or electric shock that is likely to be fatal. Only a qualified and authorized electrician is permitted to install or modify electrical installations.
5.4.1 AC
Install AC PDUs and cables in the cabinet in accordance with supplier
instructions, for instance Rittal or Eaton.
The following AC power
outlets are required:
- 2 × 3 C19 outlets for each HP enclosure
- 2 × 1 C13 outlets for each Extreme switch
- 2 × 1 C13 outlets for the EMC storage system
Make sure that the AC power source is switched off.
Connect AC power cables to the cabinet.
6 Installing Units
This section describes how to install units in the cabinet.
The location of units in the cabinet is subject to local site design and therefore not included in this document. The recommendation is to start equipping units from the bottom of the cabinet.
Be aware that all equipment will probably not fit into one cabinet, because of restrictions on weight per square meter and power consumption on the site.
6.1 Installing HP c7000 Enclosure
6.1.1 Preparing the Cabinet
Install the support hardware in the cabinet. See Site Installation documentation for information on where the units are to be installed.
Install the following components:
- Four cage nuts for the front of each enclosure. Use the cabinet template shipped with the cabinet rail kit to find the correct locations for the cage nuts.
- Cabinet rails. The left rail is marked L and the right one is marked R. The rail installs over the cabinet rack columns and locks in place without screws.
For more detailed information, refer to the installation Instructions from HP, supplied with the Enclosure.
6.1.2 Removing Units from the HP c7000 Enclosure
A fully populated enclosure can weigh up to 217.7 kg (480 lb). To make it easier to move and install the equipment, Ericsson recommends that all heavy units are removed from the HP enclosure before installation.
- Note:
- The following units do not need to be removed:
- Blanking plates and dummy units
- Insight Display
Prepare an area for the units to be removed by reusing the packing material of the enclosure.
While still keeping the enclosure on the pallet, remove components from the front and back of the enclosure.
When all components have been removed, the empty enclosure weighs about 60 kg (130 lb) and still must be handled by 2 people.
This product contains components sensitive to ESD. Use an approved ESD wrist strap, connected to the product grounding point, to avoid damaging these components.
Do the following:
- Remove the compute blades from the enclosure:
a
Open the latch by moving the latch to the right.
b
Pull out the unit by using the handle.
- Remove the power supply units (PSUs) located in the bottom
of the enclosure.
a
Press the purple button.
b
Pull out the unit using the metal handle.
Move the Insight Display to the right when removing PSU 3 and to the left when removing PSU 4.
- Remove the front plastic covers by pulling them straight
up and out. This exposes the four screws that are to be used for attaching
the enclosure to the cabinet.
- Remove the ten fans from the rear of the enclosure:
a
Twist the purple handle counterclockwise.
b
Pull out the fan unit by pulling the purple handle.
- Remove the units in interconnect bay 1 through 8:
a
Press the purple ejector button and slide it to the right to release the latch handle.(1)
b
Pull the latch handle to remove the unit. (1)
(1) The graphics illustrate the removal of a VC Flex module.
- Remove both Onboard Administrator (OA) modules:
a
Press the purple ejector button and slide it to the right to release the latch handle.
b
Pull the latch handle to remove the unit.
- Remove the OA tray:
a
Press the purple ejector button and slide it to the right to release the latch handle.
b
Pull the latch handle to remove the unit.
6.1.3 Installing the Enclosure
This section describes how to install the enclosure in the cabinet.
At least two people are required for this operation.
An empty enclosure weighs about 60 kg.
The equipment is heavy. Lifting the equipment without the aid of a lifting device can cause injury.
Do the following:
- Using both hands, slide the enclosure from the pallet to the lifting device.
- Using the lifting device, move and lift the enclosure to the position in front of the cabinet where it is to be installed.
- Slide the enclosure from the lifting device into the cabinet and onto the support brackets.
- Fasten the four front screws and tighten them according to cabinet supplier recommendations, using a torque wrench with a T25 bit.
- Reinstall the front plastic covers which snap into place.
6.1.4 Reinstalling Units
6.1.4.1 Reinstalling Rear HP Units
For more information and for the identification of the HP units, see Section 11.1.
This product contains components sensitive to ESD. Use an approved ESD wrist strap, connected to the product grounding point, to avoid damaging these components.
Install the HP enclosure units previously removed. Do the following:
- Reinstall the OA tray:
a
Insert and push the tray into the slot, making sure that the latch handle is open.
b
Shut the handle to fix the tray in the slot. Ensure that the latch is closed.
- Reinstall the OA modules:
a
Insert and push the module into the OA bay, making sure that the latch handle is open.
b
Shut the handle to fix the module in the bay. Ensure that the latch is closed.
- Reinstall modules in bays 8 through 1, starting with bay
8 and ending with bay 1, in the following layout:
Location/Bay
Units
Location/Bay
1
2
3
HP 10Gb/s Pass-Thru
HP 10Gb/s Pass-Thru
4
5
HP 10Gb/s Pass-Thru
HP 10Gb/s Pass-Thru
6
7
Interconnect Blank
Interconnect Blank
8
OA Module
OA Tray
OA Module
Reinstall the modules:
a
Without touching the front connectors, press in the units firmly with the latches open, then close the latches.(1)
b
Make sure that all latches are closed and secured.
(1) The graphics illustrate the reinstallation of a VC Flex module.
- Reinstall the fan units:
- Note:
- When installing a fan in the top row of fan slots, orient the fan so that the indicator is in the lower right corner. When installing a fan in the bottom row of fan slots, orient the fan so that the indicator is in the upper left corner.
Insert and push the fan unit into the slot, making sure that the orientation of the unit is correct.(1)
(1) The graphics illustrate the installation of a fan in the top row of fan slots.
6.1.4.2 Reinstalling Front Units
- Note:
- Make sure that all rear units have been reinstalled before reinstalling the front units.
This section describes how to reinstall the front units for the Certified Configuration with three enclosures. This configuration contains 48 blades.
Do the following:
- Install the first compute blade
to the top left bay of enclosure 0:
a
If applicable, remove the server blank from the slot.
b
If applicable, remove the back connector cover from the server by pushing the release latch and pulling the cover.
c
Insert and push the server into the slot carefully but stop before the server reaches the backplane.
d
Open the latch by moving it to the right and open the handle.
e
Push the server carefully to connect the backplane connector.
f
Shut the handle to fix the server in the slot. Ensure that the latch is closed.
- Install the remaining compute blades to all enclosures
as described in Step 1, beginning with
bay 1, and ending with bay 16 in each enclosure. The blade layout
is the following:
Install compute blades into subracks in the following layout:
Enclosure 0:
Location / Bay
1
2
3
4
5
6
7
8
First row of blades
Blade 1
Blade 2
Blade 3
Blade 4
Blade 5
Blade 6
Blade 7
Blade 8
Second row of blades
Blade 9
Blade 10
Blade 11
Blade 12
Blade 13
Blade 14
Blade 15
Blade 16
Location / Bay
9
10
11
12
13
14
15
16
Enclosure 1:
Location / Bay
1
2
3
4
5
6
7
8
First row of blades
Blade 17
Blade 18
Blade 19
Blade 20
Blade 21
Blade 22
Blade 23
Blade 24
Second row of blades
Blade 25
Blade 26
Blade 27
Blade 28
Blade 29
Blade 30
Blade 31
Blade 32
Location / Bay
9
10
11
12
13
14
15
16
Enclosure 2:
Location / Bay
1
2
3
4
5
6
7
8
First row of blades
Blade 33
Blade 34
Blade 35
Blade 36
Blade 37
Blade 38
Blade 39
Blade 40
Second row of blades
Blade 41
Blade 42
Blade 43
Blade 44
Blade 45
Blade 46
Blade 47
Blade 48
Location / Bay
9
10
11
12
13
14
15
16
- Install all six PSUs at the bottom of each HP enclosure.
Location
1
2
3
4
5
6
Power Units
PSU 1
PSU 2
PSU 3
PSU 4
PSU 5
PSU 6
- Note:
- Move the Insight display to the right when reinstalling PSU 3 and to the left when reinstalling PSU 4.
To reinstall the PSUs:
a
Insert and push the PSU into the slot carefully with the latch handle open to connect the backplane connector.
b
Shut the handle to fix the module in the slot. Ensure that the latch is closed.
6.2 Installing EMC VNX Units
This section describes how to install the EMC VNX unit. This unit is installed from the front of the cabinet.
- Prepare the location in the cabinet by installing the
following:
- Cage nuts
- Shelves, if needed
- Install the storage unit from the front.
- Tighten the screws according to cabinet manufacturer recommendations, using a torque wrench and a T30 Torx bit.
Store the serial port adapters delivered with the unit, in the cabinet. They are used when configuring the VNX.
For more information about how to install the EMC VNX unit, refer to the installation guide (P/N 300-999-781), supplied with the unit.
6.3 Installing Extreme Switches
This section describes how to install the X460V and X770 switches.
- Note:
- This unit is installed from the rear of the cabinet.
- Unpack the switch and check that it is undamaged and that all parts are included.
- Prepare the location in the cabinet. Install the following:
- Four cage nuts in the front
- Four cage nuts in the rear
- Prepare the units by installing the front cabinet mounting brackets.
- Install the unit from the rear of the cabinet.
The front panel with most of the connectors is to be facing backward on the same side as the HP enclosure rear units with all the connectors. The reason for this is to have all cabling at the same side of the cabinet. The units have fans marked AIR IN.
- Tighten the screws according to cabinet manufacturer recommendations, using a torque wrench and a T30 Torx bit.
- Install the extreme switch rear mounting brackets from the front of the cabinet and secure them to the cabinet using the supplied screws. Tighten the screws according to cabinet manufacturer recommendations, using a torque wrench and a T30 Torx bit.
For more information about installing the switches, see the documentation supplied with the unit.
7 Equipping Units with Small Form-Factor Pluggable Units
This section describes installation and location of Small Form-Factor Pluggable (SFP+) and Quad Small Form-Factor Pluggable (QSFP+) modules in the Ericsson Cloud System units.
To install an SFP+ module, do the following:
- Unpack the SFP+ module and verify that it is of the correct type (see specifications in the following tables) and that it is undamaged.
- Remove the protective plug from the port in the unit.
- Install the SFP+ module, observing correct orientation, and push it into the port until the connector mates.
- Only remove the protective plug or plugs installed on the SFP+ module when an optical fiber cable is ready to be connected.
See Section 11 for more information about the units, boards, and connectors.
7.1 HP Units
7.1.1 VC Flex Modules
This section describes how the ports in the VC Flex modules must be equipped. The ports are marked X1 to X10 as shown in Figure 7.
|
Enclosure 0 |
Enclosure 1 |
Enclosure 2 | ||||
|---|---|---|---|---|---|---|
|
Bay 1 |
Bay 2 |
Bay 1 |
Bay 2 |
Bay 1 |
Bay 2 | |
|
X1 |
||||||
7.1.2 Pass-Thru Modules in Bay 3, 4, 5, and 6
This section describes how the ports 1 - 16 must be equipped in the pass-thru modules in Bay 3 - 6.
|
Port Location in |
Type of SFP+ Module |
|---|---|
|
Bay 3, 4, 5, and 6: Ports 1-16(1) |
HP BLc10Gb SR SFP+ (455883) |
(1) Only equip ports connected to blades equipped
in the enclosure, see Table 5 for cross reference.
The internal connection in the HP enclosure is shown in Table 5.
|
Blade in Front Bay No per Enclosure |
Connected to |
Connected to |
Connected to |
Connected to |
|---|---|---|---|---|
|
1 (17,33) |
1 |
1 |
1 |
1 |
|
2 (18,34) |
2 |
2 |
2 |
2 |
|
3 (19,35) |
3 |
3 |
3 |
3 |
|
4 (20,36) |
4 |
4 |
4 |
4 |
|
5 (21,37) |
5 |
5 |
5 |
5 |
|
6 (22,38) |
6 |
6 |
6 |
6 |
|
7 (23.39) |
7 |
7 |
7 |
7 |
|
8 (24,40) |
8 |
8 |
8 |
8 |
|
9 (25,41) |
9 |
9 |
9 |
9 |
|
10 (26,42) |
10 |
10 |
10 |
10 |
|
11 (27,43) |
11 |
11 |
11 |
11 |
|
12 (28,44) |
12 |
12 |
12 |
12 |
|
13 (29,45) |
13 |
13 |
13 |
13 |
|
14 (30,46) |
14 |
14 |
14 |
14 |
|
15 (31,47) |
15 |
15 |
15 |
15 |
|
16 (32,48) |
16 |
16 |
16 |
16 |
7.2 Switch Units
This section describes how to equip ports in Extreme Switches.
|
Ports |
Type of QSFP+ Module |
|---|---|
|
Ports 1–48 |
40GBASE-SR4 QSFP+ (10319) |
|
Port 52 |
40GBASE-SR4 QSFP+ (10319) |
|
Ports 85–92(1) |
40GBASE-SR4 QSFP+ (10319) |
(1) Use 85–92 for 48 blades with
80 GB bandwidth to BGw. For 80 blades or 120 GB, use 85–100
(add 93–100).
|
Ports |
Type of QSFP+ Module |
|---|---|
|
Ports 1–48 |
40GBASE-SR4 QSFP+ (10319) |
|
Port 52 |
40GBASE-SR4 QSFP+ (10319) |
|
Ports 93–100 |
40GBASE-SR4 QSFP+ (10319) |
|
Ports |
Type of SFP+ Module |
|---|---|
|
Ports 49–50 |
SR SFP+ module (10301) |
8 Installing Internal Cables
This section describes how to connect internal cables. Mark the cables according to local requirements before connecting them.
8.1 Connecting Power Cables
Connect AC power cables from the distribution power outlets in the cabinet to the power inlet connectors on the units:
Improper electrical installation may cause fire or electric shock that is likely to be fatal. Only a qualified and authorized electrician is permitted to install or modify electrical installations.
- HP Enclosure (six cables) to the cabinet AC power distribution
bar. The supplied cables have three flat pins in the AC power distribution
bar end, use the appropriate cables for this.
C19 cables are to be used. - Storage units (two cables)
C13 cables are to be used. - Extreme switches (two per switch, six switches) to the
AC distribution units. Use two cables for each Extreme switch unit,
one to side A, and one to side B.
C13 cables are to be used.
See also Table 1 and 2 to secure redundancy when connecting the power cables.
8.2 Connecting Control Cables
This section describes how to connect the subrack management control cables.
The tables in this document include subrack management connections to the local control switch. Subrack management connections can also be connected to a separate site-specific HW management system, depending on customer solution.
Connect cables for control network between the units according to information found in the following tables.
8.2.1 Control Switch A
This section describes how to connect the control cables to control switch A.
|
From Port |
Connector |
Cable Type |
Connector |
To Enclosure |
To Unit |
To Port |
|---|---|---|---|---|---|---|
|
1 |
RJ45 |
RJ45 - RJ45 |
RJ45 |
E0 |
VC Flex B1 |
X1 |
|
9 |
RJ45 |
RJ45 - RJ45 |
RJ45 |
E1 |
VC Flex B1 |
X1 |
|
17 |
RJ45 |
RJ45 - RJ45 |
RJ45 |
E2 |
VC Flex B1 |
X1 |
|
41 |
RJ45 |
RJ45 - RJ45 |
RJ45 |
A | ||
|
42 |
RJ45 |
RJ45 - RJ45 |
RJ45 |
E0 |
left | |
|
43 |
RJ45 |
RJ45 - RJ45 |
RJ45 |
E1 |
left | |
|
44 |
RJ45 |
RJ45 - RJ45 |
RJ45 |
E2 |
left | |
|
49 |
LC/LC A1/B1 |
8f OM3 MPO-LC |
MPO |
Traffic Switch A |
52 | |
|
50 |
LC/LC A1/B1 |
8f OM3 MPO-LC |
MPO |
Storage Switch A |
52 | |
|
51 |
DAC |
Control Switch B |
51 | |||
|
52 |
DAC |
Control Switch B |
52 | |||
8.2.2 Control Switch B
This section describes how to connect the control cables to control switch B.
|
From Port |
Connector |
Cable Type |
Connector |
To Enclosure |
To Unit |
To Port |
|---|---|---|---|---|---|---|
|
1 |
RJ45 |
RJ45 - RJ45 |
RJ45 |
E0 |
VC Flex B2 |
X1 |
|
9 |
RJ45 |
RJ45 - RJ45 |
RJ45 |
E1 |
VC Flex B2 |
X1 |
|
17 |
RJ45 |
RJ45 - RJ45 |
RJ45 |
E2 |
VC Flex B2 |
X1 |
|
41 |
RJ45 |
RJ45 - RJ45 |
RJ45 |
B | ||
|
42 |
RJ45 |
RJ45 - RJ45 |
RJ45 |
E0 |
right | |
|
43 |
RJ45 |
RJ45 - RJ45 |
RJ45 |
E1 |
right | |
|
44 |
RJ45 |
RJ45 - RJ45 |
RJ45 |
E2 |
right | |
|
49 |
LC/LC A1/B1 |
8f OM3 MPO-LC |
MPO |
Traffic Switch B |
52 | |
|
50 |
LC/LC A1/B1 |
8f OM3 MPO-LC |
MPO |
Storage Switch B |
52 | |
|
51 |
Info only, cable shown
in table for Switch A. |
Control Switch A |
51 | |||
|
52 |
Control Switch A |
52 | ||||
8.3 Connecting Traffic and Storage Cables
This section describes how to connect optical cables for the Ericsson Cloud System.
Equipment that transmits laser light can cause permanent eye damage. Never look directly into the end of a fiber optic cable or other laser source. Switch off the laser before starting work on laser equipment.
- Note:
- Exercise care when handling optical cables:
- Optical cables must not be bent in a radius smaller than 50 mm.
- Do not touch the connector ends.
- Remove the protective caps in SFP+ and cable connectors before connecting them.
- Do not leave SFP+ modules and Optical connectors without the protective caps, remove caps only when they are to be connected.
Connect the optical cables as shown in the following tables.
8.3.1 Three Enclosures Using X770
The traffic and storage switch cabling for three enclosures using Extreme switch X770 and VNX5400 are shown in this section:
- Traffic switch A connections are shown in Table 11.
- Traffic switch B connections are shown in Table 12.
- Storage switch A connections are shown in Table 13.
- Storage switch B connections are shown in Table 14.
8.3.1.1 Traffic Switch A
|
From Traffic Switch A |
Connector |
Cable Type |
Connector |
To |
To |
Enclosure |
|---|---|---|---|---|---|---|
|
1–4 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
1 |
Pass-Thru, Bay 3 |
E0 |
|
LC/LC A2/B2 |
2 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A3/B3 |
3 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A4/B4 |
4 |
Pass-Thru, Bay 3 | ||||
|
5–8 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
5 |
Pass-Thru, Bay 3 | |
|
LC/LC A2/B2 |
6 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A3/B3 |
7 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A4/B4 |
8 |
Pass-Thru, Bay 3 | ||||
|
9–12 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
9 |
Pass-Thru, Bay 3 | |
|
LC/LC A2/B2 |
10 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A3/B3 |
11 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A4/B4 |
12 |
Pass-Thru, Bay 3 | ||||
|
13–16 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
13 |
Pass-Thru, Bay 3 | |
|
LC/LC A2/B2 |
14 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A3/B3 |
15 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A4/B4 |
16 |
Pass-Thru, Bay 3 | ||||
|
17–20 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
1 |
Pass-Thru, Bay 3 |
E1 |
|
LC/LC A2/B2 |
2 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A3/B3 |
3 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A4/B4 |
4 |
Pass-Thru, Bay 3 | ||||
|
21–24 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
5 |
Pass-Thru, Bay 3 | |
|
LC/LC A2/B2 |
6 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A3/B3 |
7 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A4/B4 |
8 |
Pass-Thru, Bay 3 | ||||
|
25–28 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
9 |
Pass-Thru, Bay 3 | |
|
LC/LC A2/B2 |
10 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A3/B3 |
11 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A4/B4 |
12 |
Pass-Thru, Bay 3 | ||||
|
29–32 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
13 |
Pass-Thru, Bay 3 | |
|
LC/LC A2/B2 |
14 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A3/B3 |
15 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A4/B4 |
16 |
Pass-Thru, Bay 3 | ||||
|
33–36 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
1 |
Pass-Thru, Bay 3 |
E2 |
|
LC/LC A2/B2 |
2 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A3/B3 |
3 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A4/B4 |
4 |
Pass-Thru, Bay 3 | ||||
|
37–40 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
5 |
Pass-Thru, Bay 3 | |
|
LC/LC A2/B2 |
6 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A3/B3 |
7 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A4/B4 |
8 |
Pass-Thru, Bay 3 | ||||
|
41–44 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
9 |
Pass-Thru, Bay 3 | |
|
LC/LC A2/B2 |
10 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A3/B3 |
11 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A4/B4 |
12 |
Pass-Thru, Bay 3 | ||||
|
45–48 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
13 |
Pass-Thru, Bay 3 | |
|
LC/LC A2/B2 |
14 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A3/B3 |
15 |
Pass-Thru, Bay 3 | ||||
|
LC/LC A4/B4 |
16 |
Pass-Thru, Bay 3 | ||||
|
85–88 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
BGw A 4 × 10GE |
||
|
LC/LC A2/B2 |
BGw A 4 × 10GE |
|||||
|
LC/LC A3/B3 |
BGw A 4 × 10GE |
|||||
|
LC/LC A4/B4 |
BGw A 4 × 10GE |
|||||
|
89–92 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
BGw A 4 × 10GE |
||
|
LC/LC A2/B2 |
BGw A 4 × 10GE |
|||||
|
LC/LC A3/B3 |
BGw A 4 × 10GE |
|||||
|
LC/LC A4/B4 |
BGw A 4 × 10GE |
|||||
|
101 |
DAC |
101 |
Traffic Switch B |
|||
|
102 |
DAC |
102 |
Traffic Switch B |
|||
8.3.1.2 Traffic Switch B
|
From Traffic Switch B |
Connector |
Cable Type |
Connector |
To |
To Unit |
Enclosure |
|---|---|---|---|---|---|---|
|
1–4 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
1 |
Pass-Thru, Bay 4 |
E0 |
|
LC/LC A2/B2 |
2 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A3/B3 |
3 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A4/B4 |
4 |
Pass-Thru, Bay 4 | ||||
|
5–8 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
5 |
Pass-Thru, Bay 4 | |
|
LC/LC A2/B2 |
6 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A3/B3 |
7 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A4/B4 |
8 |
Pass-Thru, Bay 4 | ||||
|
9–12 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
9 |
Pass-Thru, Bay 4 | |
|
LC/LC A2/B2 |
10 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A3/B3 |
11 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A4/B4 |
12 |
Pass-Thru, Bay 4 | ||||
|
13–16 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
13 |
Pass-Thru, Bay 4 | |
|
LC/LC A2/B2 |
14 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A3/B3 |
15 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A4/B4 |
16 |
Pass-Thru, Bay 4 | ||||
|
17–20 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
1 |
Pass-Thru, Bay 4 |
E1 |
|
LC/LC A2/B2 |
2 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A3/B3 |
3 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A4/B4 |
4 |
Pass-Thru, Bay 4 | ||||
|
21–24 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
5 |
Pass-Thru, Bay 4 | |
|
LC/LC A2/B2 |
6 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A3/B3 |
7 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A4/B4 |
8 |
Pass-Thru, Bay 4 | ||||
|
25–28 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
9 |
Pass-Thru, Bay 4 | |
|
LC/LC A2/B2 |
10 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A3/B3 |
11 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A4/B4 |
12 |
Pass-Thru, Bay 4 | ||||
|
29–32 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
13 |
Pass-Thru, Bay 4 | |
|
LC/LC A2/B2 |
14 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A3/B3 |
15 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A4/B4 |
16 |
Pass-Thru, Bay 4 | ||||
|
33–36 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
1 |
Pass-Thru, Bay 4 |
E2 |
|
LC/LC A2/B2 |
2 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A3/B3 |
3 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A4/B4 |
4 |
Pass-Thru, Bay 4 | ||||
|
37–40 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
5 |
Pass-Thru, Bay 4 | |
|
LC/LC A2/B2 |
6 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A3/B3 |
7 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A4/B4 |
8 |
Pass-Thru, Bay 4 | ||||
|
41–44 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
9 |
Pass-Thru, Bay 4 | |
|
LC/LC A2/B2 |
10 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A3/B3 |
11 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A4/B4 |
12 |
Pass-Thru, Bay 4 | ||||
|
45–48 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
13 |
Pass-Thru, Bay 4 | |
|
LC/LC A2/B2 |
14 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A3/B3 |
15 |
Pass-Thru, Bay 4 | ||||
|
LC/LC A4/B4 |
16 |
Pass-Thru, Bay 4 | ||||
|
85–88 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
BGw B 4 × 10GE |
||
|
LC/LC A2/B2 |
BGw B 4 × 10GE |
|||||
|
LC/LC A3/B3 |
BGw B 4 × 10GE |
|||||
|
LC/LC A4/B4 |
BGw B 4 × 10GE |
|||||
|
89–92 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
BGw B 4 × 10GE |
||
|
LC/LC A2/B2 |
BGw B 4 × 10GE |
|||||
|
LC/LC A3/B3 |
BGw B 4 × 10GE |
|||||
|
LC/LC A4/B4 |
BGw B 4 × 10GE |
|||||
|
101 |
Info only, cable shown in table for Traffic Switch A |
101 |
Traffic Switch A |
|||
|
102 |
102 |
Traffic Switch A |
||||
8.3.1.3 Storage Switch A
|
From Storage Switch A |
Connector |
Cable |
Connector |
To |
To |
To |
|---|---|---|---|---|---|---|
|
1–4 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
1 |
Pass-Thru, Bay 5 |
E0 |
|
LC/LC A2/B2 |
2 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A3/B3 |
3 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A4/B4 |
4 |
Pass-Thru, Bay 5 | ||||
|
5–8 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
5 |
Pass-Thru, Bay 5 | |
|
LC/LC A2/B2 |
6 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A3/B3 |
7 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A4/B4 |
8 |
Pass-Thru, Bay 5 | ||||
|
9–12 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
9 |
Pass-Thru, Bay 5 | |
|
LC/LC A2/B2 |
10 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A3/B3 |
11 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A4/B4 |
12 |
Pass-Thru, Bay 5 | ||||
|
13–16 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
13 |
Pass-Thru, Bay 5 | |
|
LC/LC A2/B2 |
14 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A3/B3 |
15 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A4/B4 |
16 |
Pass-Thru, Bay 5 | ||||
|
17–20 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
1 |
Pass-Thru, Bay 5 |
E1 |
|
LC/LC A2/B2 |
2 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A3/B3 |
3 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A4/B4 |
4 |
Pass-Thru, Bay 5 | ||||
|
21–24 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
5 |
Pass-Thru, Bay 5 | |
|
LC/LC A2/B2 |
6 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A3/B3 |
7 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A4/B4 |
8 |
Pass-Thru, Bay 5 | ||||
|
25–28 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
9 |
Pass-Thru, Bay 5 | |
|
LC/LC A2/B2 |
10 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A3/B3 |
11 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A4/B4 |
12 |
Pass-Thru, Bay 5 | ||||
|
29–32 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
13 |
Pass-Thru, Bay 5 | |
|
LC/LC A2/B2 |
14 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A3/B3 |
15 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A4/B4 |
16 |
Pass-Thru, Bay 5 | ||||
|
33–36 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
1 |
Pass-Thru, Bay 5 |
E2 |
|
LC/LC A2/B2 |
2 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A3/B3 |
3 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A4/B4 |
4 |
Pass-Thru, Bay 5 | ||||
|
37–40 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
5 |
Pass-Thru, Bay 5 | |
|
LC/LC A2/B2 |
6 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A3/B3 |
7 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A4/B4 |
8 |
Pass-Thru, Bay 5 | ||||
|
41–44 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
9 |
Pass-Thru, Bay 5 | |
|
LC/LC A2/B2 |
10 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A3/B3 |
11 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A4/B4 |
12 |
Pass-Thru, Bay 5 | ||||
|
45–48 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
13 |
Pass-Thru, Bay 5 | |
|
LC/LC A2/B2 |
14 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A3/B3 |
15 |
Pass-Thru, Bay 5 | ||||
|
LC/LC A4/B4 |
16 |
Pass-Thru, Bay 5 | ||||
|
93–96 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
LC/LC A1 - 0 |
Storage |
|
|
LC/LC A2/B2 |
LC/LC A2 - 0 |
Storage |
||||
|
LC/LC A3/B3 |
Not |
|||||
|
LC/LC A4/B4 |
Not |
|||||
|
97–100 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
B1 - 0 |
Storage |
|
|
LC/LC A2/B2 |
B2 - 0 |
Storage |
||||
|
LC/LC A3/B3 |
Not |
|||||
|
LC/LC A4/B4 |
Not |
|||||
|
101 |
DAC |
101 |
Storage Switch B |
|||
|
102 |
DAC |
102 |
Storage Switch B |
|||
8.3.1.4 Storage Switch B
|
From Storage Switch B |
Connector |
Cable Type |
Connector |
To |
To Unit |
Enclosure |
|---|---|---|---|---|---|---|
|
1–4 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
1 |
Pass-Thru, Bay 6 |
E0 |
|
LC/LC A2/B2 |
2 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A3/B3 |
3 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A4/B4 |
4 |
Pass-Thru, Bay 6 | ||||
|
5–8 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
5 |
Pass-Thru, Bay 6 | |
|
LC/LC A2/B2 |
6 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A3/B3 |
7 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A4/B4 |
8 |
Pass-Thru, Bay 6 | ||||
|
9–12 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
9 |
Pass-Thru, Bay 6 | |
|
LC/LC A2/B2 |
10 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A3/B3 |
11 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A4/B4 |
12 |
Pass-Thru, Bay 6 | ||||
|
13–16 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
13 |
Pass-Thru, Bay 6 | |
|
LC/LC A2/B2 |
14 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A3/B3 |
15 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A4/B4 |
16 |
Pass-Thru, Bay 6 | ||||
|
17–20 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
1 |
Pass-Thru, Bay 6 |
E1 |
|
LC/LC A2/B2 |
2 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A3/B3 |
3 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A4/B4 |
4 |
Pass-Thru, Bay 6 | ||||
|
21–24 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
5 |
Pass-Thru, Bay 6 | |
|
LC/LC A2/B2 |
6 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A3/B3 |
7 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A4/B4 |
8 |
Pass-Thru, Bay 6 | ||||
|
25–28 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
9 |
Pass-Thru, Bay 6 | |
|
LC/LC A2/B2 |
10 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A3/B3 |
11 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A4/B4 |
12 |
Pass-Thru, Bay 6 | ||||
|
29–32 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
13 |
Pass-Thru, Bay 6 | |
|
LC/LC A2/B2 |
14 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A3/B3 |
15 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A4/B4 |
16 |
Pass-Thru, Bay 6 | ||||
|
33–36 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
1 |
Pass-Thru, Bay 6 |
E2 |
|
LC/LC A2/B2 |
2 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A3/B3 |
3 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A4/B4 |
4 |
Pass-Thru, Bay 6 | ||||
|
37–40 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
5 |
Pass-Thru, Bay 6 | |
|
LC/LC A2/B2 |
6 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A3/B3 |
7 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A4/B4 |
8 |
Pass-Thru, Bay 6 | ||||
|
41–44 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
9 |
Pass-Thru, Bay 6 | |
|
LC/LC A2/B2 |
10 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A3/B3 |
11 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A4/B4 |
12 |
Pass-Thru, Bay 6 | ||||
|
45–48 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
13 |
Pass-Thru, Bay 6 | |
|
LC/LC A2/B2 |
14 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A3/B3 |
15 |
Pass-Thru, Bay 6 | ||||
|
LC/LC A4/B4 |
16 |
Pass-Thru, Bay 6 | ||||
|
93–96 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
LC/LC A1 - 1 |
Storage |
|
|
LC/LC A2/B2 |
LC/LC A2 - 1 |
Storage |
||||
|
LC/LC A3/B3 |
Not |
|||||
|
LC/LC A4/B4 |
Not |
|||||
|
97–100 |
MPO |
8f OM3 MPO-LC |
LC/LC A1/B1 |
B1 - 1 |
Storage |
|
|
LC/LC A2/B2 |
B2 - 1 |
Storage |
||||
|
LC/LC A3/B3 |
Not |
|||||
|
LC/LC A4/B4 |
Not |
|||||
|
101 |
Info only, cable shown in table for Storage Switch A |
101 |
Storage Switch A |
|||
|
102 |
102 |
Storage Switch A |
||||
8.3.1.5 Enclosure Cables
|
From |
Cable |
To | ||
|---|---|---|---|---|
|
Enclosure |
Port |
Port |
Enclosure | |
|
E0 |
Link up |
RJ45 |
Link down |
E1 |
|
E1 |
Link up |
RJ45 |
Link down |
E2 |
9 Powering On
This section describes how to power on the Ericsson Cloud System.
Do the following:
- Make sure that all units and fuses on the PDUs are switched off.
- Switch on the AC power outside the cabinet.
- Switch on the fuses for the storage system on the PDU and switch on the storage system main switch.
- Switch on the fuses for the control switches on the PDU and switch on the AC power switch on the control switches.
- Switch on the fuses for the storage and traffic switches on the PDU and switch on the AC power switch on the storage and traffic switches.
- Switch on the fuses for the HP enclosures and switch on the AC power switch on the HP systems.
- Verify that the indicators are on for all units in the cabinet. Refer to instructions supplied with each unit for information about the interpretation of the indicators.
- Report any findings to the implementation project.
10 Post Installation Activities
10.1 Concluding Routines
Before leaving the site, perform the following procedure:
- Clean the site and remove objects such as wrapping paper and cable clippings.
- Dispose of waste in accordance with local regulations.
- Fill in the verification checklist in the Site Installation Documentation.
- Report any faults according to local requirements.
- Lock Cabinets (if applicable).
- Hand over the Site Installation Documentation to the person responsible for the site.
- Lock all doors and gates to the site.
Ericsson strongly recommends that installers pay particular attention to the environment when cleaning the site after installation. In particular, recycle all waste that can be recycled, and sort the rest so that they can be disposed of in accordance with local regulations. Use the checklist in Table 16 to recycle and sort waste after the procedures in this instruction have been completed.
|
Recycle or Sort As |
Item |
YES |
N/A |
|---|---|---|---|
|
Metals |
Nuts, bolts, washers, and screws |
||
|
Pieces of cable with high metallic content |
|||
|
Waste metal from cable ladders |
|||
|
Paper |
Paper |
||
|
Plastics |
Bubble plastic |
||
|
Cable insulation from crimping, brazing, or welding |
|||
|
Cable tie clippings |
|||
|
Foam |
|||
|
Packing chips |
|||
|
Pieces of cable with low metallic content |
|||
|
Polystyrene |
|||
|
Wood |
Wood |
||
|
Notes: | |||
- Report to the implementation project that the hardware installation is complete and that the system is ready for software installation.
11 Reference Information
This section contains drawings showing the connectors on the related units.
- Note:
- All illustrations in this document are examples. The actual appearance can differ depending on the hardware ordered.
11.1 HP Enclosure and Units
The HP c7000 Enclosure and the contained units are explained by the figures and tables of this section.
Figure 9 HP c7000 Enclosure, Front Side
|
Item |
Description |
|---|---|
|
A |
HP Blade, bay 1 |
|
B |
Space for HP Blade, bay 8 |
|
C |
PSU, one of six |
|
D |
Insight display |
Figure 10 HP Enclosure Rear Side
|
Position |
Bay |
Description |
|---|---|---|
|
A and B |
1 and 2 |
|
|
C, D, E, and F |
3, 4, 5, and 6 |
|
|
G and H |
7 and 8 |
Not used, interconnect blanks |
|
J |
Left |
|
|
K |
Right |
|
|
L |
Enclosure control |
OA tray. Enclosure link-down and link-up ports |
Ports 1 - 16 must be equipped with the applicable SPF+ modules.
11.2 Switches
11.2.1 Extreme Switch X460
The X460 switch front contains 48 RJ-45 ports and 4 SFP+ cages which can be equipped with SFP+ modules.
The rear of the X460 switch has air intakes for the fans and AC power inlets.
|
Pos |
Description |
|---|---|
|
1 |
Fans, three are used for redundancy. |
|
2 |
Power Units (AC shown). Two power units are used for redundancy. |
11.2.2 Extreme Switch X770
The X770 switch has 32 QSFP+ cages in the front panel. Each QSFP+ has four LC connectors or one MPO-8f connector. In this application, the switch is equipped with QSPF modules in a configuration with connectors 1 through 104 as shown in Figure 16.
The rear of the X770 switch has air intakes for the fans and AC power or DC power inlets.
|
Pos |
Description |
|---|---|
|
1 |
FAN units, up to five are used for redundancy. |
|
2 |
Power Units (AC shown). Two power units are used for redundancy. |
11.3 Storage Units
EMC VNX5400
Reference List
| [1] Safety Rules for Work with Power, Climate and Energy-Supervision Equipment, 2/1550-CNH 10803 Uen, available at Ericsson support |