Data Path Connection Failure
Cloud Execution Environment

Contents

1Introduction
1.1Alarm Description
1.2Prerequisites

2

Procedure
2.1Actions
2.2Collect Troubleshooting Data

Reference List

1   Introduction

This instruction concerns alarm handling.

1.1   Alarm Description

This section describes the Data Path Connection Failure alarm.

The Data Path Connection Failure alarm is issued by the Managed Object (MO) DstDPN when the data path connectivity is lost between:

Note:  
The Cloud SDN Controller (CSC) generates this alarm only if the Cloud SDN Switch (CSS) switch port failure affects DPN connectivity.

The severity of the alarm is CRITICAL.

Possible alarm causes and fault locations are explained in Table 1.

Table 1    Alarm Causes

Alarm
Cause

Description

Fault
Reason

Fault
Location

Impact

Data path connectivity is lost between:


The data path connectivity is lost between a pair of CSSs.

  • Hardware fault

  • Network fault

CSS

The service provided by the component is degraded or lost.

The following is the consequence for the node if the alarm is not solved:

The alarm attributes are listed in Table 2.

Table 2    Alarm Attributes

Attribute Name

Attribute Value

Major Type

193

Minor Type

2162690

Managed Object Class

DstDPN

Managed Object Instance

Region=<name_of_the_region>,
Service=SDNc,
Alarm=DataPathConnectionFailure,
SrcDPN=<dpn_id>,
DstDPN=<dpn_id>
(1)


or


Region=<name_of_the_region>,
Service=SDNc,
Alarm=DataPathConnectionFailure
srcDevice=<openflow_source_device_id>
-dstDevice=<openflow_ip_address>
_ipv4Address=Ipv4Address
_value=<ip_address>
-tunnelTypeVXLAN
(2)


or


Region=<name_of_the_region>,
Service=SDNc,
Alarm=DataPathConnectionFailure
srcDevice=<openflow_source_device_id>
-dstDevice=<hwvtep_uuid>
-tunnelTypeVXLAN
(3)

Specific Problem

SDNc, data path connectivity between DPNs is lost

Event Type

communicationsAlarm

Probable Cause

302

Additional Text

:<hw_uuid_of_corresponding_server>:<hw_uuid_of_corresponding_server>(1)


or


:<hw_uuid_of_corresponding_server>:IpAddress(2)


or


:<hw_uuid_of_corresponding_server>(3)

Severity

CRITICAL

(1)  When the connectivity is lost between DPNs.

(2)  When the connectivity is lost between DPN and DC-GW.

(3)  When the connectivity is lost between DPN and HW-VTEP.


1.2   Prerequisites

This section provides information on the documents, tools, and conditions that apply to the procedure.

1.2.1   Documents

For more information on SDN alarms, refer to the following SDN documents:

1.2.2   Tools

No tools are required.

1.2.3   Conditions

Not applicable.

2   Procedure

This section describes the procedure to follow when this alarm is received.

2.1   Actions

2.1.1   Actions for Data Path Connection Failure Between DPNs

Do the following:

  1. Identify the affected compute servers:
    1. Note down the HW UUIDs from the Additional Text field of the alarm.
    2. Match the HW UUIDs to the specific compute server with one of the following tools:
  2. On source and destination CSS hosts, check the status of CSS.
    1. service openvswitch-switch status

      If CSS is down, restart it.

      Note:  
      Restarting CSS causes all VMs to restart.

      service openvswitch-switch start

    2. Check whether data connectivity between the source and destination CSSs is operational:

      ping <destination_css_ip>

      An example output where the ping is successful is shown below.

      cic-1:~ # ping 10.184.22.13
      PING 10.184.22.13 (10.184.22.13) 56(84) bytes of data.
      64 bytes from 10.184.22.13: icmp_seq=1 ttl=254 time=1.03 ms
      64 bytes from 10.184.22.13: icmp_seq=2 ttl=254 time=0.867 ms
      64 bytes from 10.184.22.13: icmp_seq=3 ttl=254 time=0.780 ms
      ^C
      --- 10.184.22.13 ping statistics ---
      3 packets transmitted, 3 received, 0% packet loss, time 2002ms
      rtt min/avg/max/mdev = 0.780/0.895/1.038/0.107 ms

      An example output where the ping fails is shown below.

      cic-1:~ # ping 10.184.22.99
      PING 10.184.22.99 (10.184.22.99) 56(84) bytes of data.
      ^C
      --- 10.184.22.99 ping statistics ---
      6 packets transmitted, 0 received, 100% packet loss, time 5038ms

      If the ping fails, this can indicate an underlay fault. Refer to alarm topic LostConnection in the HDS documentation, Reference [3], and continue with Section 2.2.

    If the connection is reestablished and the alarm ceases, exit this procedure. Else, continue with Section 2.2.

2.1.2   Actions for Data Path Connection Failure Between DPN and DC-GW

Do the following:

  1. Identify the affected compute servers:
    1. Note down the HW UUID of the source device and the IP address of the destination device from the alarm output.
    2. Match the HW UUID to the specific compute server with one of the following tools:
  2. On source and destination CSS hosts, check the status of CSS.
    1. service openvswitch-switch status

      If CSS is down, restart it.

      Note:  
      Restarting CSS causes all VMs to restart.

      service openvswitch-switch start

    2. Check whether data connectivity between the CSS and the DC-GW is operational:

      ping <destination_dc-gw_ip>

      If the ping fails, this can indicate an underlay fault. Refer to alarm topic LostConnection in the HDS documentation, Reference [3], and continue with Section 2.2.

    If the connection is reestablished and the alarm ceases, exit this procedure. Else, continue with Section 2.2.

2.1.3   Data Path Connection Failure Between DPN and HW-VTEP

Do the following:

  1. Identify the affected compute servers:
    1. From the alarm output, note down the following data:
      • HW UUID of the source device
      • Node ID of the destination device
      • Name of the destination HW-VTEP device

        An example for the HW-VTEP device name is the following:

        hwvtep://uuid/<node_id>/physicalswitch/<device_name>hwvtep://uuid/<node_id>/physicalswitch/⇒
        <device_name>

    2. Match the HW UUID to the specific compute server with one of the following tools:
  2. On source and destination CSS hosts, check the status of CSS.
    1. service openvswitch-switch status

      If CSS is down, restart it.

      Note:  
      Restarting CSS causes all VMs to restart.

      service openvswitch-switch start

    2. Check whether data connectivity between the CSS and the HW-VTEP is operational:

      ping <destination_hwvtep_device_ip>

      If the ping fails, this can indicate an underlay fault. Refer to alarm topic LostConnection in the HDS documentation, Reference [3], and continue with Section 2.2.

    If the connection is reestablished and the alarm ceases, exit this procedure. Else, continue with Section 2.2.

2.2   Collect Troubleshooting Data

If the connection is not reestablished, follow the below steps:

  1. Collect troubleshooting data as described in the Data Collection Guideline.
  2. Contact the next level of maintenance support.

    Further actions are outside the scope of this instruction.

  3. The job is completed.