1 Introduction
This instruction concerns alarm handling.
This document is only applicable for systems using Extreme switches configured dynamically by the Cloud Execution Environment (CEE). Refer to the Configuration File Guide for more information about the CEE configuration types.
1.1 Alarm Description
The alarm is issued by the Managed Object (MO) Fan when malfunction occurs in one or more cooling fans in the physical switch.
The severity of the alarm is CRITICAL.
The possible alarm causes and fault locations are described in Table 1.
|
Alarm |
Description |
Fault |
Fault |
Impact |
|---|---|---|---|---|
|
Cooling fan or fans are down |
Failure of one or more cooling fans in physical switch. |
Fan module is faulty |
Switch fan module |
Cooling |
The following is the consequence for the node if the alarm is not solved:
- Cooling malfunction in the physical switch.
The alarm attributes are listed in Table 2.
|
Attribute Name |
Attribute Value |
|---|---|
|
Major Type |
193 |
|
Minor Type |
2031685 |
|
Managed Object Class |
Fan |
|
Managed Object Instance |
Region=<name_of_the_region>, |
|
Specific Problem |
Fan Failure |
|
Event Type |
equipmentAlarm (5) |
|
Probable Cause |
m3100CoolingFanFailure(107) |
|
Additional Text |
Failure of one or more cooling fans in ToR switch.(1) |
|
Severity |
CRITICAL (3) |
(1) Top of Rack (ToR) stands for the physical
switch.
1.2 Prerequisites
This section provides information on the documents, tools, and conditions that apply to the procedure.
1.2.1 Documents
Before starting this procedure, ensure that the following document is available:
Summit Family Hardware Installation Guide, Reference [1].
1.2.2 Tools
No tools are required.
1.2.3 Conditions
No conditions.
2 Procedure
This section describes the procedure to follow when this alarm is received.
2.1 Actions
Perform the following:
- Locate the faulty fan module or modules by using the <fan_id> attribute from the Source field of the alarm.
- Confirm that the fan module or modules are not functioning properly, or are down.
- Replace the failed fan module or modules in the switch by referring to the instructions in Summit Family Hardware Installation Guide, Reference [1].
- Confirm that the alarm has ceased.
If the alarm ceases, exit this procedure.
If the alarm persists, proceed to Step 5.
- Collect troubleshooting data as described in the Data Collection Guideline.
- Consult the next level of maintenance
support.
Further actions are outside the scope of this instruction.
- The job is completed.